Chapter 4: Description of functions (abbreviated)
73
PC.50
Time unit of a simple PLC
0: S (seconds)
1: H (hours)
0
PC.51
Source 0
0: Set from PC.00
1: FIV
2: FIC
3: FIA
4: PULSE setting (X5)
5: PID
6: Set according to the preset frequency
(P0.10), modified with ter. UP / DOWN
0
Group PD: Communication parameters
PD.00
Transfer speed
Units: MODBUS
0:300 BPS
1:600 BPS
2:1200 BPS
3:2400 BPS
4:4800 BPS
5:9600 BPS
6:19200 BPS
7:38400 BPS
8:57600 BPS
9:115200 BPS
Tens: Reserved
Hundreds: Reserved
Thousands: Reserved
6005
PD.01
Data format
0: No parity, data format <8, N, 2>
1: Even parity, data format <8, E, 1>
2: Odd parity, data format <8,0,1>
3: No parity, data format <8, N, 1> Applies to
MODBUS
3
PD.02
Local address
1 247; 0: Transmitting address
1