Chapter 4: Description of functions (abbreviated)
57
P8.08
Deceleration 4
0.0s - 6500.0s
By the
model
P8.09
Jump frequency 1
0.00Hz maximum frequency
0.00Hz
Function
code
Parameter name
Setting range
Default
setting
Property
P8.10
Jump frequency 2
0.00Hz maximum frequency
0.00 Hz
P8.11
Amplitude of the jump
frequency
0.00Hz maximum frequency
0.01Hz
P8.12
Dead zone time when
changing rotation
0.0s - 3000.0s
0.0s
P8.13
Control of reverse run
0: Enabled
1: Disabled
0
P8.14
Mode of operation when
the set frequency is
lower than the lower
limit of frequency
0: RUN at the lower frequency limit
1: STOP
2: RUN at zero speed
0
P8.15
Balance control
0.00Hz - 10.00Hz
0.00Hz
P8.16
Limit of total turn-on
time
0h - 65000h
Oh
P8.17
Total time of operation
the inverter
0h - 65000h
Oh
P8.18
The protection at the
start
0: NO
1: YES
0
P8.19
Frequency detection
value (FDT1)
0.00Hz maximum frequency
50.00Hz
P8.20
Hysteresis detection
value (FDH)
0.0% - 100.0% (FDT1)
5.0%
P8.21
Achieved range of
frequency detection
0.00Hz 100% (maximum frequency)
0.0%