Chapter 4: Description of functions (abbreviated)
59
P8.38
Current reaching the
value 1
0.0 300.0 % (rated motor current)
100.0%
P8.39
Current reaching the
value of amplitude 1
0.0 300.0 % (rated motor current)
0.0%
P8.40
Current reaching the
value 2
0.0 300.0 % (rated motor current)
100.0%
P8.41
Current reaching the
value of amplitude 2
0.0 300.0 % (rated motor current)
0.0%
P8.42
Selection of timing
function
0: Enabled
1: Disabled
0
P8.43
Timing source selection
0: P8.44
1: FIV
2: FIC
3: Reserved
100% of the analog input corresponds to
P8.44
0
P8.44
Time of duration
0.0 min - 6500.0 min
0.0 min
P8.45
Lower limit of input
voltage FIV
0.00V-P8.46
3.10V
P8.46
Upper limit of input
voltage FIV
P8.45-10.00V
6.80V
P8.47
Thermal protection
switch-off temperature
0°C - 150°C
100°C
P8.48
Fan control
0: The fan works only during operation
1: The fan works continuously
0
P8.49
Frequency at wake-up
Frequency during sleep (P8.51) maximum
frequency (P0.12)
0.00Hz
P8.50
Delay of wake-up
0.0s - 6500.0s
0.0s
P8.51
Frequency during sleep
0.00 Hz - frequency at wake-up (P8.49)
0.00Hz
P8.52
Delay of sleep
0.0s - 6500.0s
0.0s
P8.53
Running time reached
0.0Min - 6500.0Min
0.0 min