Watlow Series F4P Communications ■ 9.9
2622 Reset 1A, Cascade PID Set 2
r/w 0 to 9999 repeats per minute (in hundredths)
2642 Reset 1A, Cascade PID Set 3
r/w 0 to 9999 repeats per minute (in hundredths)
2662 Reset 1A, Cascade PID Set 4
r/w 0 to 9999 repeats per minute (in hundredths)
2682 Reset 1A, Cascade PID Set 5
r/w 0 to 9999 repeats per minute (in hundredths)
502 Reset 1A, PID Set 1
r/w 0 to 9999 repeats per minute (in hundredths)
512 Reset 1A, PID Set 2
r/w 0 to 9999 repeats per minute (in hundredths)
522 Reset 1A, PID Set 3
r/w 0 to 9999 repeats per minute (in hundredths)
532 Reset 1A, PID Set 4
r/w 0 to 9999 repeats per minute (in hundredths)
542 Reset 1A, PID Set 5
r/w 0 to 9999 repeats per minute (in hundredths)
2612 Reset 1B, Cascade PID Set 1
r/w 0 to 9999 repeats per minute (in hundredths)
2632 Reset 1B, Cascade PID Set 2
r/w 0 to 9999 repeats per minute (in hundredths)
2652 Reset 1B, Cascade PID Set 3
r/w 0 to 9999 repeats per minute (in hundredths)
2672 Reset 1B, Cascade PID Set 4
r/w 0 to 9999 repeats per minute (in hundredths)
2692 Reset 1B, Cascade PID Set 5
r/w 0 to 9999 repeats per minute (in hundredths)
552 Reset 1B, PID Set 1
r/w 0 to 9999 repeats per minute (in hundredths)
562 Reset 1B, PID Set 2
r/w 0 to 9999 repeats per minute (in hundredths)
572 Reset 1B, PID Set 3
r/w 0 to 9999 repeats per minute (in hundredths)
582 Reset 1B, PID Set 4
r/w 0 to 9999 repeats per minute (in hundredths)
592 Reset 1B, PID Set 5
r/w 0 to 9999 repeats per minute (in hundredths)
1601 Restore Calibration, Inputs 1-3
w0Yes (Input 1)
1Yes (Input 2)
2Yes (Input 3)
20 Retransmit 1, Diagnostic
r0None
4Process
21 Retransmit 2, Diagnostic
r0None
4Process
709 Retransmit Source, Retransmit Output 1
r/w 0 Off
1 Input 1
2 Input 2
3 Input 3
4 Set Point
5 Channel 1 Power
726 Retransmit Source, Retransmit Output 2
r/w 0 Off
1 Input 1
2 Input 2
3 Input 3
4 Set Point
5 Channel 1 Power
4 Revision, Diagnostic
r 0.00 to 9.99
25 Save Changes to EE
w0Save
681 Scale High, Analog Input 1
r/w Depends on sensor and decimal point selection.
683 Scale High, Analog Input 2
r/w Depends on sensor and decimal point selection.
685 Scale High, Analog Input 3
r/w Depends on sensor and decimal point selection.
680 Scale Low, Analog Input 1
r/w Depends on sensor and decimal point selection.
682 Scale Low, Analog Input 2
r/w Depends on sensor and decimal point selection.
684 Scale Low, Analog Input 3
r/w Depends on sensor and decimal point selection.
712 Scale Offset, Retransmit Output 1
r/w -9999 to 9999
Range Low to Range High
729 Scale Offset, Retransmit Output 2
r/w -9999 to 9999
Range Low to Range High
693 Scaling, Input 1
r/w 0 Normal Scaling
1 Inverse Scaling
694 Scaling, Input 2
r/w 0 Normal Scaling
1 Inverse Scaling
695 Scaling, Input 3
r/w 0 Normal Scaling
1 Inverse Scaling
600 Sensor, Analog Input 1
r/w 0 Thermocouple
1RTD
2Process
610 Sensor, Analog Input 2
r/w 0 Thermocouple
1RTD
2Process
4Off
620 Sensor, Analog Input 3
r/w 0 Thermocouple
1RTD
2Process
3 Slidewire
4Off
1 Serial Number (first part), Diagnostic
r 000000 to 999999
2 Serial Number (second part), Diagnostic
r 000000 to 999999
299 Set Differential Value
r/w -19999 to 30000
300 Set Point 1, Main Page
r/w Value
603 Set Point High Limit, Analog Input 1
r/w Depends on Sensor
613 Set Point High Limit, Analog Input 2
r/w Depends on Sensor
623 Set Point High Limit, Analog Input 3
r/w Depends on Sensor
602 Set Point Low Limit, Analog Input 1
r/w Depends on Sensor
612 Set Point Low Limit, Analog Input 2
r/w Depends on Sensor
622 Set Point Low Limit, Analog Input 3
r/w Depends on Sensor
1300 Set Point, Set Lockout
r/w 0 Full Access
1 Read Only
301 Set Ratio Value
r/w
1330-33 Set/Change Password, Set Lockout
r/w Four characters, ASCII codes 0-9, A-Z
1302 Setup Page, Set Lockout
r/w 0 Full Access
1 Read Only
2 Password
3 Hidden