A.2 Appendix Watlow Series F4P
Universal Analog Inputs 1 (2 and 3 optional)
Update rates, IN1 = 20Hz, IN2 and IN3 = 10Hz
Thermocouple
•Type J, K, T, N, C (W5), E, PTII, D (W3), B, R, S
RTD
2- or 3-wire platinum, 100, 500 or 1000
JIS or DIN curves, 1.0 or 0.1 indication
Process
Input resolution 50,000 bits at full scale
Range selectable: 0-10VÎ (dc), 0-5VÎ (dc), 1-5VÎ (dc),
0-50mV, 0-20mA, 4-20mA
•Voltage input impedance 20K
Current input impedance 100
Digital Inputs (4)
Update rate = 10Hz
Contact or dc voltage
10K input impedance
Control Outputs (1A, 1B)
Update rate = 20Hz
Open Collector/Switched dc
Internal load switching (nominal):
Switched dc, 22 to 28VÎ (dc), limited @ 30mA
External load switching max.:
Open collector 42VÎ (dc) @ 0.5A
Solid-state Relay
Zero switched, optically coupled, 0.5A @ 24VÅ(ac)
minimum, 253VÅ(ac) maxi.
Electromechanical Relay
Form C, 2A @ 250VÅ(ac) or 30VÎ (dc) max.
Resistive or inductive load
•Without contact suppression
Process Outputs (Optional Retransmit)
Update rate = 1Hz
User-selectable 0-10VÎ (dc), 0-5VÎ (dc),
1-5VÎ (dc) @1K min., 0-20mA, 4-20mA @ 800 max.
Resolution:
dc ranges = 2.5mV nominal
mA ranges = 5µA nominal
Calibration accuracy:
dc ranges = ±15mV
mA ranges = ±30µA
•Temperature stability 100ppm/°C
Alarm Outputs
Output update rate1Hz
Electromechanical relay, Form C, 2A @ 30VÎ (dc) or
240VÅ(ac) maximum
Communications
EIA-232 and EIA-485 serial communications with
Modbus™ RTU protocol
Safety and Agency Approvals
•UL®/C-UL 916-listed, File # E185611
Process Control Equipment
CE
EN 61010-1
EN 61326
EN 55011
NEMA 4X and IP65
Terminals
•Touch-safe, removable terminal blocks, accepts 12 to
22-gauge wire
Dimensions
•Width x height x depth
3.93 in x 3.93 in x 3.85 in panel mount
(99 mm x 99 mm x 97 mm)
Power
100-240VÅ(ac), -15%, +10%; 50/60Hz, ±5%
24-28Vı(ac/dc), -15%, +10% (order option)
39VA maximum power consumption
Data retention upon power failure via nonvolatile
memory.
Sensor input isolation from input to input to output to
communication circuitry is 500VÅ (ac).
Operating Environment
32 to 149°F (0 to 65°C)
•0 to 90% RH, non-condensing
Storage temperature: -40 to 158°F (-40 to 70°C)
Accuracy
Calibration accuracy and sensor conformity: ±0.1% of
span ±1°C @ 77°F ±5°F (25°C ±3°C) ambient, and rated
line voltage ±10% with the following exceptions:
Type T, 0.12% of span for -200°C to -50°C
Types R and S, 0.15% of span for 0°C to 100°C
Type B, 0.24% of span for 870°C to 1700°C
Accuracy span: Less than or equal to operating ranges,
1000°F/540°C minimum
•Temperature stability: ±0.1°F/°F (±0.1°C/°C) rise in
ambient for thermocouples
•±0.05°F/°F (±0.05°C/°C) rise in ambient for RTD sensors
Displays
Process: 5, seven-segment LED red
Control interface display: high-definition LCD green
Sensor Operating Ranges
Type J: 32 to 1500°F or 0 to 815°C
Type K: -328 to 2500°F or -200 to 1370°C
Type T: -328 to 750°F or -200 to 400°C
Type N: 32 to 2372°F or 0 to 1300°C
Type E: -328 to 1470°F or -200 to 800°C
Type C: 32 to 4200°F or 0 to 2315°C
Type D: 32 to 4352°F or 0 to 2400°C
Type PTII: 32 to 2543°F or 0 to 1395°C
Type R: 32 to 3200°F or 0 to 1760°C
Type S: 32 to 3200°F or 0 to 1760°C
Type B: 32 to 3300°F or 0 to 1816°C
RTD (DIN): -328 to 1472°F or -200 to 800°C
RTD (JIS): -328 to 1166°F or -200 to 800°C
Process: -19999 to 30000 units
Sensor Accuracy Ranges:
Input ranges
Type J: 32 to 1382°F or 0 to 750°C
Type K: -328 to 2282°F or -200 to 1250°C
Type T: -328 to 662°F or -200 to 350°C
Type N: 32 to 2282°F or 0 to 1250°C
Type E: -328 to 1470°F or -200 to 800°C
Type C(W5) 32 to 4200°F or 0 to 2315°C
Type D(W3) 32 to 4352°F or 0 to 2400°C
Type PTII: 32 to 2540°F or 0 to 1393°C
Type R: 32 to 2642°F or 0 to 1450°C
Type S: 32 to 2642°F or 0 to 1450°C
Type B: 1598 to 3092°F or 870 to 1700°C
RTD (DIN): -328 to 1472°F or -200 to 800°C
RTD (JIS): -328 to 1166°F or -200 to 630°C
Process:-19999 to 30000 units
UL
®
is a registered trademark of Underwriter’s Laboratories,
Inc.
NOTE: Specifications subject to change without notice.