8.10 ■ Installation and Wiring Watlow Series F4P
Outputs 1A and 1B
Figure 8.10a — Solid-state Relay
24VÅ (ac) minimum, 253VÅ (ac) maximum
0.5 amps, off-state impedance 31MΩ
Figure 8.10b — Switched DC, Open Collector
• Switched dc configuration (COM not used)
DC+ is 22 to 28VÎ (dc)
Maximum supply current is 30mA
• Open collector output (dc+ not used)
DC- is 42VÎ (dc) maximum
Off: 10mA maximum leakage
On: 0.2V @ 0.5 amps sink
Figure 8.10c — 0-20mA, 4-20mA, 0-5VÎ, 1-5VÎ and 0-10VÎ (dc)
Process
mA maximum load impedance is 800Ω
VÎ (dc) minimum load impedance is 1KΩ
43 COM. -
40 COM. -
COM.
COM.
43 COM.
40 COM.
COM.
42 N.O.
43 COM.
39 N.O.
40 COM.