EasyManua.ls Logo

Watlow F4P Series

Watlow F4P Series
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow Series F4P Parameters 6.5
Note: For more information about how parameter set-
tings affect the controller’s operation, see the Features
Chapter.
* None of the B parameters are active if both outputs are
set to cool or heat.
Operations Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default (I/O, Set) Parameters to Appear
Active if Control Type (Analog
Input 3) is set to Cascade, PID
Units (Setup Page) is set to SI
and Proportional Band is not
set to 0.*
1A 1B Set
2601 2611 [1]
2621 2631 [2]
2641 2651 [3]
2661 2671 [4]
2681 2691 [5]
r/w
0 minutes0.00 to 99.99 minutes
(0 to 9999)
Integral x (A or B)
Set the integral time in
minutes.
[or]
Active if Control Type (Analog
Input 3) is set to Cascade.*
1A 1B Set
2600 2610 [1]
2620 2630 [2]
2640 2650 [3]
2660 2670 [4]
2680 2690 [5]
r/w
25°F
14°C
0 to 30000
0.0 to 3000.0
0.00 to 300.00
0.000 to 30.000
(0 to 30000) in integer,
tenths, hundredths or
thousandths
Proportional Band x (A or
B)
Define the proportional
band for PID control.
Main > Operations > Edit PID > Cascade Outer Loop PID Set X (1 to 5)
Cascade Outer Loop PID Set x (1 to 5)
* None of the B parameters are active if both outputs are set to cool or heat.
Active if Proportional Band is set
to 0 and one output is set to
heat and the other to cool
(Setup Page).* Based on dial
setting.
1A 1B Set
507 557 [1]
517 567 [2]
527 577 [3]
537 587 [4]
547 597 [5]
r/w
30 to 30000
0.0 to 3000.0
0.00 to 300.00
0.000 to 30.000
(0 to 30000) in integer,
tenths, hundredths or
thousandths
Hysteresis x (A or B)
Define the process vari-
able change from the set
point required to re-en-
ergize the output (in on-
off mode).
Active if Proportional Band is not
set to 0 and one output is set to
heat and the other to cool
(Setup Page).* Based on decimal
setting.
1A 1B Set
505 555 [1]
515 565 [2]
525 575 [3]
535 585 [4]
545 595 [5]
r/w
00 to 30000
0.0 to 3000.0
0.00 to 300.00
0.000 to 30.000
(0 to 30000) in integer,
tenths, hundredths or
thousandths
Dead Band x (A or B)
Define the effective shift
in the heating and cool-
ing set points to prevent
conflict.
Active if PID Units (Setup Page)
is set to U.S. and Proportional
Band is not set to 0.*
1A 1B Set
504 554 [1]
514 564 [2]
524 574 [3]
534 584 [4]
544 594 [5]
r/w
0.00 minutes0.00 to 9.99 minutes
(0 to 999)
Rate x (A or B)
Set the rate time.
Active if PID Units (Setup Page)
is set to SI and Proportional
Band is not set to 0.*
1A 1B Set
503 553 [1]
513 563 [2]
523 573 [3]
533 583 [4]
543 593 [5]
r/w
0.00 minutes0.00 to 9.99 minutes
(0 to 999)
Derivative x (A or B)
Set the derivative time.
Active if PID Units (Setup Page)
is set to U.S. and Proportional
Band is not set to 0.*
1A 1B Set
502 552 [1]
512 562 [2]
522 572 [3]
532 582 [4]
542 592 [5]
r/w
0 per minute0.00 per minute to
99.99 per minute
(0 to 9999)
Reset x (A or B)
Set the reset time in re-
peats per minute.
Active if PID Units (Setup Page)
is set to SI and Proportional
Band is not set to 0.*
1A 1B Set
501 551 [1]
511 561 [2]
521 571 [3]
531 581 [4]
541 591 [5]
r/w
0 minutes0.00 to 99.99 minutes
(0 to 9999)
Integral x (A or B)
Set the integral time in
minutes.
[or]

Table of Contents

Related product manuals