6.26 Parameters Watlow Series F4P
Note: For more information about how parameter settings affect
the controller’s operation, see the Features Chapter.
Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default (I/O, Set) Parameters to Appear
Active: Always.
1315 r/w
Yes (0)
Clear Locks
Unlock set point and all
pages and menus.
Active: Always.
1330 [1]
1331 [2]
1332 [3]
1333 [4]
r/w
none4 characters
Set/Change Password
Reset or change pass-
word. Choose Yes to
change the password.
Active: Always.
1303 r/w
Full Access
(0)
Full Access (0)
Read Only (1)
Password (2)
Factory Page
Set access to this page.
Active: Always.
1302r/w
Full Access
(0)
Full Access (0)
Read Only (1)
Password (2)
Hidden (3)
Setup Page
Set access to this page.
Active: Always.
1308 r/w
Full Access
(0)
Full Access (0)
Read Only (1)
Password (2)
Hidden (3)
Operations, Alarm Set
Point
Set access to this menu.
Active: Always.
1307 r/w
Full Access
(0)
Full Access (0)
Read Only (1)
Password (2)
Hidden (3)
Operations, Edit PID
Set access to this menu.
Active: Always.
1306 r/w
Full Access
(0)
Full Access (0)
Read Only (1)
Password (2)
Hidden (3)
Operations, Autotune PID
Set access to this menu.
Active: Always.
1300 r/w
Full Access
(0)
Full Access (0)
Read Only (1)
Set Point
Set the set point
access level.
Main > Factory > Set Lockout
Set Lockout
Factory Page Parameters

Table of Contents