6.28 ■ Parameters Watlow Series F4P
✔ Note: Press the Information Key ˆ for more task-related tips.
Factory Page Parameter Table Modbus
Register
Range read/write Conditions for
Parameter Description (Modbus Value) Default (I/O, Set) Parameters to Appear
Active: Always.1514 wAll Off (0)
Output 1A (1)
Output 1B (2)
Retransmit 1 (5)
Retransmit 2 (6)
Alarm 1 (7)
Alarm 2 (8)
All On (9)
Communications (10)
Test Outputs
Choose output to test.
Main > Factory > Test
Test
Active: Always.1515 rxx
(xx)
Line Frequency
Display the ac line fre-
quency in hertz.
Active: Always.
Input
1500 [1]
1531 [2]
1531 [3]
r
xx.x
(xxx)
CJCx (1 to 3) Temp
Cold junction compensa-
tion for the analog input.
Reads the ambient tem-
perature of the controller.
Active: Always.
Input
1501 [1]
1532 [2]
1532 [3]
r
HHHH
CJCx (1 to 3) A to D
Factory use only.
Active: Always.
Input
1504 [1]
1505 [2]
1506 [3]
r
HHHH
Input x (1 to 3) A to D
Factory use only.
Active: Always.
Retransmit
20 [1]
21 [2]
r
None (0)
Process (4)
Retransmit x (1 or 2)
Displays the retransmit
option.
Active: Always.
Output
16 [1A]
17 [1B]
r
None (0) [Out 1B only]
Mechanical Relay (1)
SSR (2)
DC (3)
Process (4)
Output x (1A or 1B)
Displays the output type.
Active: Always.10 rUniv Dual (8)
None (0)
Input 3
Displays the input 3
type.
Active: Always.9 rUniv Dual (8)
None (0)
Input 2
Displays the input 2
type.