Watlow PM LEGACY™ Limit Controller 103 Appendix
Indication Description Possible Cause(s) Corrective Action
Alarm High
AL.h1
AL.h2
AL.h3
AL.h4
Sensor input above
high alarm set point
Temperature is greater
than alarm set point
Alarm is set to latching and
an alarm occurred in the
past
Incorrect alarm set point
Incorrect alarm source
Check cause of over tem-
perature
Clear latched alarm
Establish correct alarm set
point
Set alarm source to proper
setting
Error Input
Er.i1
Sensor does not pro-
vide a valid signal to
controller
Sensor improperly wired or
open
Incorrect setting of sensor
type
Calibration corrupt
Correct wiring or replace
sensor
Match setting to sensor
used
Check calibration of con-
troller
Ambient Error
Er.ab
Sensor does not pro-
vide a valid signal to
controller
Ambient error - cold junc-
tion circuitry not working
Return to factory for repair
Limit won’t
clear or reset
Limit will not clear or
reset with keypad or
digital input
Sensor input is out of limit
set point range
Limit set point is incorrect
Digital input function is in-
correct
Correct cause of sensor in-
put out of limit range
Set limit set point to correct
trip point
Set digital input function
and source instance
Limit Error
Li.E1
Limit state cannot be
determined due to
lack of sensor input,
limit will trip
Sensor improperly wired or
open
Incorrect setting of sensor
type
Calibration corrupt
Correct wiring or replace
sensor
Match setting to sensor
used
Check calibration of con-
troller
Limit Low
Li.L1
Sensor input below
low limit set point
Temperature is less than
limit set point
Limit outputs latch and re-
quire reset
Incorrect alarm set point
Check cause of under tem-
perature
Clear limit
Establish correct limit set
point
Limit High
Li.h1
Sensor input above
high limit set point
Temperature is greater
than limit set point
Limit outputs latch and re-
quire reset
Incorrect alarm set point
Check cause of over tem-
perature
Clear limit
Establish correct limit set
point