Watlow PM LEGACY™ Limit Controller 56 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
Fi
Fi
Digital Input (5 to 6)
Function Instance
Select which Digital
Input will be triggered
by a true state.
0 to 40 0 Instance 5
Map 1 Map 2
1326 1566
Offset to next
instance (Map
1 & Map 2)
equals +20
0x6E
(110)
5 to 6
4
139 10004 uint
RWES
LiЛЏ
sEt
Limit Menu
L.sd
L.Sd
Limit
Sides
Select which side or
sides of the process
value will be moni-
tored.
both Both (13)
high High (37)
LoФІ Low (53)
Both Instance 1
Map 1 Map 2
688 728
0x70
(112)
1
5
40 12005 uint
RWES
L.hy
L.hy
Limit
Hysteresis
Set the hysteresis for
the limit function. This
determines how far
into the safe range the
process value must
move before the limit
can be cleared.
0.001 to
9,999.000°F or
units
0.001 to
5,555.000°C
3.0°F or
units
2.0°C
Instance 1
Map 1 Map 2
682 722
0x70
(112)
1
2
41 12002 float
RWES
sp.Lh
SP.Lh
Limit
Maximum Set Point
Set the high end of the
limit set point range.
-1,999.000 to
9,999.000
9,999.000 Instance 1
Map 1 Map 2
696 736
0x70
(112)
1
9
42 12009 float
RWES
sp.LL
SP.LL
Limit
Minimum Set Point
Set the low end of the
limit set point range.
-1,999.000 to
9,999.000
-1,999.000 Instance 1
Map 1 Map 2
698 738
0x70
(112)
1
0xA (10)
43 12010 float
RWES
Lh.s
Lh.S
Limit
High Limit Set Point
Set the high process
value that will trigger
the limit.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1 Map 2
686 726
0x70
(112)
1
4
39 12004 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set