Watlow PM LEGACY™ Limit Controller 75 Chapter 7 Factory Page
Factory Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
In-
dex
Param-
eter
ID
Data
Type
and Ac-
cess **
Cust
fcty
Custom
par
Par
Custom
Parameter 1 to
20
Select the param-
eters that will ap-
pear in the Home
Page.
The Parameter 1
value will appear
in the upper dis-
play of the Home
Page. It cannot
be changed with
the Up and Down
Keys in the Home
Page.
The Parameter 2
value will appear
in the lower dis-
play in the Home
Page. It can be
changed with the
Up and Down
Keys, if the pa-
rameter is a writ-
able one.
Scroll through the
other Home Page
parameters with
the Advance Key.
Note:
Display Pairs af-
fect the pairing
of custom pa-
rameters on the
Home page. For
more information
on Display Pairs
see the section in
this guide entitled
"Modifying the
Display Pairs".
nonE None
LL.S Low Limit Set
Point
Lh.S High Limit Set
Point
L.hy Limit Hysteresis
L.St Limit Status
Pro Process
i.CA Calibration Off-
set
C_F Display Units
USr.r Replace Settings
From
A.Lo Low Set Point
A.hi High Set Point
A.hy Hysteresis
CUSt Custom Menu
See:
Home
Page
- - - - - - - - - -
- -
14005 uint
RWES
** R: Read, W: Write, E: EEPROM, S: User Set