Watlow PM LEGACY™ Limit Controller 45 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fib-
us
In-
dex
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
dio
opEr
Digital Input/Output Menu
do.s
do.S
Digital Output (5 to 6)
Output State
View the state of
this output.
off Off (62)
on On (63)
- - - - Instance 5
Map 1 Map 2
1012 1132
Offset to
next instance
equals +30
0x6A (106)
5 to 6
7
46 6007 uint
R
di.s
di.S
Digital Input (5 to 6)
Input State
View this event in-
put state.
off Off (62)
on On (63)
- - - - Instance 5
Map 1 Map 2
1020 1140
Offset to
next instance
equals +30
0x6A (106)
5 to 6
0x0B (11)
- - - - 6011 uint
R
Ei.s
Ei.S
Digital Input (5 to 6)
Event Status
View this event input
state.
ϸAct Inactive (41)
act Active (5)
- - - - Instance 5
Map 1 Map 2
1408 1648
Offset to
next instance
equals +20
0x6E (110)
5 to 6
5
140 10005 uint
R
No Dis-
play
EZ-Key/s (1 to 2)
Event Status
View this event input
state.
ϸAct Inactive (41)
act Active (5)
- - - - Instance 1
Map 1 Map 2
1328 1568
Instance 2
Map 1 Map 2
1348 1588
0x6E (110)
3 to 4
5
140 10005 uint
R
LiЛЏ
opEr
Limit Menu
LL.s
LL.S
Limit
Low Limit Set
Point
Set the low process
value that will trig-
ger the limit.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1 Map 2
684 724
0x70 (112)
1
3
38 12003 float
RWES
Lh.s
Lh.S
Limit
High Limit Set
Point
Set the high pro-
cess value that will
trigger the limit.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1 Map 2
686 726
0x70 (112)
1
4
39 12004 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set