Watlow PM LEGACY™ Limit Controller 60 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
r.hi
r.hi
Output Process (3)
Range High
Set the maximum val-
ue of the retransmit
value range in process
units. When the re-
transmit source is at
this value, the retrans-
mit output will be at its
Scale High value.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
100.0°F
or units
38.0°C
Instance 3
Map 1Map 2
822 942
0x76
(118)
3
0x0C
(12)
102 18012 float
RWES
o.CA
o.CA
Output Process (3)
Calibration Offset
Set an offset value for
a process output.
-1,999.000 to
9,999.000°F or
units
-1,110.555 to
5,555.000°C
0.0°F or
units
0.0°C
Instance 3
Map 1Map 2
812 932
0x76
(118)
3
7
105 18007 float
RWES
ALЛЏ
SEt
Alarm Menu
A.ty
A.ty
Alarm (1 to 4)
Type
Select whether the
alarm trigger is a fixed
value or will track the
set point.
oFF Off (62)
Pr.AL Process
Alarm (76)
Off Instance 1
Map 1Map 2
1508 1908
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
0xF (15)
20 9015 uint
RWES
Sr.A
Sr.A
Alarm (1 to 4)
Alarm Source
Select what will trigger
this alarm.
Ai Analog Input
(142)
Analog
Input
Instance 1
Map 1Map 2
1512 1912
Offset to next
instance (Map
1 +50, Map 2
+60)
0x6D
(109)
1 to 4
0x11
(17)
21 9017 uint
RWES
** R: Read, W: Write, E: EEPROM, S: User Set