Watlow PM LEGACY™ Limit Controller 46 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fib-
us
In-
dex
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
LCr
LCr
Limit (1)
Clear Limit
Clear limit once limit
condition is cleared.
Clear (0)
No Change (255)
- - - -
Instance 1
Map 1 Map 2
680 720
0x70 (112)
1
1
- - - - 12014 uint
W
L.st
L.St
Limit (1)
Limit Status
Reflects whether or
not the limit is in a
safe or failed mode..
faiL Fail (32)
safE Safe (1667)
- - - -
Instance 1
Map 1 Map 2
- - - - 744
0x70 (112)
1
0x0D (13)
- - - - 12013 uint
R
No Dis-
play
Limit
Limit State
Clear limit once limit
condition is cleared.
Off (62)
None (61)
Limit High (51)
Limit Low (52)
Error (225)
- - - -
Instance 1
Map 1 Map 2
690 730
0x70 (112)
1
6
- - - - 12006 uint
R
aLЛЏ
opEr
Alarm Menu
a.Lo
A.Lo
Alarm (1 to 4)
Low Set Point
If Type (Setup
Page, Alarm Menu)
is set to:
Process - set the
process value that
will trigger a low
alarm.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
32.0°F
or units
0.0°C
Instance 1
Map 1Map 2
1482 1882
Offset to next
instance (Map
1) equals +50
Offset to next
instance (Map
2) equals +60
0x6D
(109)
1 to 4
2
18
9002 float
RWES
a.hi
A.hi
Alarm (1 to 4)
High Set Point
If Type (Setup
Page, Alarm Menu)
is set to:
Process - set the
process value that
will trigger a high
alarm.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
300.0
°F or
units
150.0
°C
Instance 1
Map 1Map 2
1480 1880
Offset to next
instance (Map
1) equals +50
Offset to next
instance (Map
2) equals +60
0x6D
(109)
1 to 4
1
19
9001 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set