Watlow PM LEGACY™ Limit Controller 110 Appendix
CIP Implicit Assembly Structures
CIP Implicit Assembly Structures
Originator (Master) to Target (PML)
Assem-
bly
Mem-
bers
Assembly
Class, Instance,
Attribute
ST Data
Type
Parameter
Parameter
Class, Instance,
Attribute
PLC
Data Type
1 0x77, 0x01, 0x01 DINT
Control Loop 1, User Control
Mode
0x97, 0x01, 0x01 DINT
2 0x77, 0x01, 0x02 DINT Closed Loop Set Point 0x6B, 0x01, 0x01 REAL
3 0x77, 0x01, 0x03 DINT Open Loop Set Point 0x6B, 0x01, 0x02 REAL
4 0x77, 0x01, 0x04 DINT Alarm 1 - Alarm High Set Point 0x6D, 0x01, 0x01 REAL
5 0x77, 0x01, 0x05 DINT Alarm 1 - Alarm Low Set Point 0x6D, 0x01, 0x02 REAL
6 0x77, 0x01, 0x06 DINT Alarm 2 - Alarm High Set Point 0x6D, 0x02, 0x01 REAL
7 0x77, 0x01, 0x07 DINT Alarm 2 - Alarm Low Set Point 0x6D, 0x02, 0x02 REAL
8 0x77, 0x01, 0x08 DINT Alarm 3 - Alarm High Set Point 0x6D, 0x03, 0x01 REAL
9 0x77, 0x01, 0x09 DINT Alarm 3 - Alarm Low Set Point 0x6D, 0x03, 0x02 REAL
10 0x77, 0x01, 0x0A DINT Alarm 4 - Alarm High Set Point 0x6D, 0x04, 0x01 REAL
11 0x77, 0x01, 0x0B DINT Alarm 4 - Alarm Low Set Point 0x6D, 0x04, 0x02 REAL
12 0x77, 0x01, 0x0C DINT Profile Action Request 0x7A, 0x01, 0x0B DINT
13 0x77, 0x01, 0x0D DINT Profile Start 0x7A, 0x01, 0x01 DINT
14 0x77, 0x01, 0x0E DINT Heat Proportional Band 0x97, 0x01, 0x06 REAL
15 0x77, 0x01, 0x0F DINT Cool Proportional Band 0x97, 0x01, 0x07 REAL
16 0x77, 0x01, 0x10 DINT Time Integral 0x97, 0x01, 0x08 REAL
17 0x77, 0x01, 0x11 DINT Time Derivative 0x97, 0x01, 0x09 REAL
18 0x77, 0x01, 0x12 DINT Heat Hysteresis 0x97, 0x01, 0x0B REAL
19 0x77, 0x01, 0x13 DINT Cool Hysteresis 0x97, 0x01, 0x0C REAL
20 0x77, 0x01, 0x14 DINT Dead Band 0x97, 0x01, 0x0A REAL
21 0x77, 0x02, 0x15 DINT None Specified - - - - - - - -
22 0x77, 0x02, 0x16 DINT None Specified - - - - - - - -
23 0x77, 0x02, 0x17 DINT None Specified - - - - - - - -
24 0x77, 0x02, 0x18 DINT None Specified - - - - - - - -
25 0x77, 0x02, 0x19 DINT None Specified - - - - - - - -
26 0x77, 0x02, 0x1A DINT None Specified - - - - - - - -
27 0x77, 0x02, 0x1B DINT None Specified - - - - - - - -
28 0x77, 0x02, 0x1C DINT None Specified - - - - - - - -
29 0x77, 0x02, 0x1D DINT None Specified - - - - - - - -
30 0x77, 0x02, 0x1E DINT None Specified - - - - - - - -
31 0x77, 0x02, 0x1F DINT None Specified - - - - - - - -
32 0x77, 0x02, 0x20 DINT None Specified - - - - - - - -
33 0x77, 0x02, 0x21 DINT None Specified - - - - - - - -
34 0x77, 0x02, 0x22 DINT None Specified - - - - - - - -
35 0x77, 0x02, 0x23 DINT None Specified - - - - - - - -
36 0x77, 0x02, 0x24 DINT None Specified - - - - - - - -
37 0x77, 0x02, 0x25 DINT None Specified - - - - - - - -
38 0x77, 0x02, 0x26 DINT None Specified - - - - - - - -
39 0x77, 0x02, 0x27 DINT None Specified - - - - - - - -
40 0x77, 0x02, 0x28 DINT None Specified - - - - - - - -
Note:
PM revision 15 and above firmware allows for 40 implicit members. Revisions below 15, allow for a
maximum of 20.
These require the user to change the defaults for Limit when utilized.