EasyManua.ls Logo

Watlow PM LEGACY PM3 - Analog Input Menu

Watlow PM LEGACY PM3
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow PM LEGACY™ Limit Controller 51 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
Ai
sEt
Analog Input Menu
sEn
SEn
Analog Input
Sensor Type
Set the analog sensor
type to match the de-
vice wired to this input.
Note:
There is no open
sensor protection for
process inputs.
off Off (62)
tC Thermocouple
(95)
ЛЏu Millivolts (56)
voLt Volts dc
(104)
ЛЏa
Milliamps dc
(112)
r0.1H RTD 100 Ω
(113)
r1.0H RTD 1,000
Ω (114)
pot Potentiome-
ter 1 kΩ (155)
thEr Thermistor
(229)
Thermo-
couple or
Thermis-
tor
Instance 1
Map 1 Map 2
368 368
0x68
(104)
1
5
3 4005 uint
RWES
Lin
Lin
Analog Input
TC Linearization
Set the linearization to
match the thermocou-
ple wired to this input.
b B (11) H K (48)
C C (15) n N (58)
d D (23) r R (80)
E E (26) s S (84)
f F (30) tT (93)
J J (46)
J Instance 1
Map 1 Map 2
370 370
0x68
(104)
1
6
4 4006 uint
RWES
rt.L
rt.L
Analog Input
RTD Leads
Set to match the
number of leads on
the RTD wired to this
input.
2 2 (1)
3 3 (2)
2 Instance 1
Map 1 Map 2
372 372
0x68
(104)
1
7
- - - - 4007 uint
RWES
Unit
Unit
Analog Input
Units
Set the type of units
the sensor will mea-
sure.
a.tp Absolute
Temperature
(1540)
rh Relative Hu-
midity (1538)
pro Process (75)
PФІr Power (73)
Process Instance 1
Map 1 Map 2
- - - - 442
0x68
(104)
1
0x2A
(42)
5 4042 uint
RWES
** R: Read, W: Write, E: EEPROM, S: User Set