Watlow PM LEGACY™ Limit Controller 52 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
s.Lo
S.Lo
Analog Input
Scale Low
Set the low scale for
process inputs. This
value, in millivolts,
volts or milliamps,
will correspond to the
Range Low output of
this function block.
-100.00 to
100.00
0.0 Instance 1
Map 1 Map 2
388 388
0x68
(104)
1
0xF (15)
6 4015 float
RWES
s.hi
S.hi
Analog Input
Scale High
Set the high scale for
process inputs. This
value, in millivolts,
volts or milliamperes,
will correspond to the
Range High output of
this function block.
-100.00 to
100.00
20.0 Instance 1
Map 1 Map 2
390 390
0x68
(104)
1
0x10
(16)
7 4016 float
RWES
r.Lo
r.Lo
Analog Input
Range Low
Set the low range for
this function block's
output.
-1,999.000 to
9,999.000
0.0 Instance 1
Map 1 Map 2
392 392
0x68
(104)
1
0x11
(17)
8 4017 float
RWES
r.hi
r.hi
Analog Input
Range High
Set the high range for
this function block's
output.
-1,999.000 to
9,999.000
9,999 Instance 1
Map 1 Map 2
394 394
0x68
(104)
1
0x12
(18)
9 4018 float
RWES
p.EE
P.EE
Analog Input
Process Error Enable
Turn the Process Error
Low feature on or off.
off Off (62)
LoФІ Low (53)
Off Instance 1
Map 1 Map 2
418 418
0x68
(104)
1
0x1E
(30)
10 4030 uint
RWES
p.EL
P.EL
Analog Input
Process Error Low
Value
If the process value
drops below this value,
it will trigger an input
error.
-100.00 to
100.00
0.0 Instance 1
Map 1 Map 2
420 420
0x68
(104)
1
0x1F
(31)
11 4031 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set