Watlow PM LEGACY™ Limit Controller 59 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
Fi
Fi
Output Process (3)
Function Instance
Set the instance of
the function selected
above.
1 to 4 1 Instance 3
Map 1Map 2
806 926
0x76
(118)
3
4
98 18004 uint
RWES
S.Lo
S.Lo
Output Process (3)
Scale Low
Set the scale low
for process output
in electrical units.
This value; in volts or
milliamps, will corre-
spond to range low
retransmit output.
-100.0 to 100.0 0.00 Instance 3
Map 1Map 2
816 936
0x76
(118)
3
9
99 18009 float
RWES
S.hi
S.hi
Output Process (3)
Scale High
Set the scale high for
process output in
electrical units. This
value; in volts or
milliamps, will corre-
spond to range high
retransmit output.
-100.0 to 100.0 10.00 Instance 3
Map 1Map 2
818 938
0x76
(118)
3
0x0A
(10)
100 18010 float
RWES
r.Lo
r.Lo
Output Process (3)
Range Low
Set the minimum value
of the retransmit value
range in process units.
When the retransmit
source is at this value,
the retransmit output
will be at its Scale
Low value.
-1,999.000 to
9,999.000°F or
units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18°C
Instance 3
Map 1Map 2
820 940
0x76
(118)
3
0x0B
(11)
101 18011 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set