Watlow PM LEGACY™ Limit Controller 58 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
otpt
SEt
Output Menu
Fn
Fn
Output Digital (1 to 4)
Function
Select what function
will drive this output.
Note:
Output 2 is always a
limit. Use as primary
limit connection. On-
ly Output 1. May also
be specified as limit.
oFF Off (62)
LiЛЏ Limit (126)
ALЛЏ Alarm (6)
Output 1
- Alarm
Output 2
- Limit
Output 3
- Off
Output 4
- Off
Instance 1
Map 1Map 2
888 1008
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A
(106)
1 to 4
5
83 6005 uint
RWES
Fi
Fi
Output Digital (1 to 4)
Output Function In-
stance
Set the instance of
the function selected
above.
1 to 4 1 Instance 1
Map 1Map 2
890 1010
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A
(106)
1 to 4
6
84 6006 uint
RWES
o.ty
o.ty
Output Process (3)
Type
Select whether the
process output will
operate in volts or
milliamps.
uoLt Volts (104)
ЛЏA Milliamps
(112)
Volts Instance 3
Map 1Map 2
800 920
0x76
(118)
3
1
95 18001 uint
RWES
Fn
Fn
Output Process (3)
Function
Set the type of func-
tion that will drive this
output.
oFF Off (62)
rЛЏt Retransmit
(213)
ALЛЏ Alarm (6)
Off Instance 3
Map 1Map 2
802 922
0x76
(118)
3
2
96 18002 uint
RWES
r.Sr
r.Sr
Output Process (3)
Retransmit Source
Select the value that
will be retransmitted.
Ai Analog Input
(142)
Analog
Input
Instance 3
Map 1Map 2
804 924
0x76
(118)
3
3
97 18003 uint
RWES
** R: Read, W: Write, E: EEPROM, S: User Set