Watlow PM LEGACY™ Limit Controller 105 Appendix
Indication Description Possible Cause(s) Corrective Action
Device Error
100
rEtn
Controller displays
internal malfunction
message at power
up.
Controller defective
Sensor input over driven
Replace or repair controller
Check sensors for ground
loops, reverse wiring or out
of range values.
Menus inacces-
sible
Unable to access
sEt, opEr, fCty
menus or particular
prompts in Home
Page
Security set to incorrect
level
Digital input set to lockout
keypad
Custom parameters incor-
rect
Check
LoC
settings in Fac-
tory Page and enter appro-
priate password in
ULoC
setting in Factory Page
Change state of digital in-
put
Change custom parameters
in Factory Page
Function Key/s
do not work
Function Key/s do
not activate required
function
Function Key function in-
correct
Function Key function in-
stance not correct
Keypad malfunction
Verify Function Key function
in the Setup Menu
Correct and change the
function instance if not cor-
rect
Replace or repair controller
Displayed value
to low
uaL.L
Value to low to be
displayed in 4 digit
LED display <-1999
Incorrect setup Check scaling of source
data
Displayed value
to high
uaL.h
Value to high to be
displayed in 4 digit
LED display >9999
• Incorrect setup • Check scaling of source
data