Watlow PM LEGACY™ Limit Controller 108 Appendix
Modbus - Programmable Memory Blocks
Assembly Definition Addresses and Assembly Working Addresses
Assembly Definition
Addresses
Assembly Working
Addresses
Assembly
Definition Addresses
Assembly
Working Addresses
40 & 41 200 & 201 80 & 81 240 & 241
42 & 43 202 & 203 82 & 83 242 & 243
44 & 45 204 & 205 84 & 85 244 & 245
46 & 47 206 & 207 86 & 87 246 & 247
48 & 49 208 & 209 88 & 89 248 & 249
50 & 51 210 & 211 90 & 91 250 & 251
52 & 53 212 & 213 92 & 93 252 & 253
54 & 55 214 & 215 94 & 95 254 & 255
56 & 57 216 & 217 96 & 97 256 & 257
58 & 59 218 & 219 98 & 99 256 & 259
60 & 61 220 & 221 100 & 101 260 & 261
62 & 63 222 & 223 102 & 103 262 & 263
64 & 65 224 & 225 104 & 105 264 & 265
66 & 67 226 & 227 106 & 107 266 & 267
68 & 69 228 & 229 108 & 109 268 & 269
70 & 71 230 & 231 110 & 111 270 & 271
72 & 73 232 & 233 112 & 113 272 & 273
74 & 75 234 & 235 114 & 115 274 & 275
76 & 77 236 & 237 116 & 117 276 & 277
78 & 79 238 & 239 118 & 119 278 & 279
Pointer 1 = 1880 & 1881
Loop Control Mode
Registers 40 & 41
Registers 200 & 201
Registers 42 & 43
Registers 202 & 203
Registers 44 & 45 Registers 204 & 205
Registers 46 & 47
Registers 206 & 207
Registers 48 & 49
Registers 208 & 209
Registers 50 & 51 Registers 210 & 211
Registers 52 & 53 Registers 212 & 213
Registers 54 & 55 Registers 214 & 215
Registers 56 & 57
Registers 216 & 217
Registers 58 & 59 Registers 218 & 219
Value of Pointer 1
Pointer 2 = 2160 & 2161
Closed Loop Set Point
Value of Pointer 2
Pointer 3 = 2162 & 2163
Open Loop Set Point
Value of Pointer 3
Pointer 4 = 1480 & 1481
Alarm 1 High Set Point
Value of Pointer 4
Pointer 5 = 1482 & 1483
Alarm 1 Low Set Point
Value of Pointer 5
Pointer 6 = 1530 & 1531
Alarm 2 High Set Point
Value of Pointer 6
Pointer 7 = 1532 & 1533
Alarm 2 Low Set Point
Value of Pointer 7
Pointer 8 = 1580 & 1581
Alarm 3 High Set Point
Value of Pointer 8
Pointer 9 = 1582 & 1583
Alarm 3 Low Set Point
Value of Pointer 9
Pointer 10 = 1630 & 1631
Alarm 4 High Set Point
Value of Pointer 10
Assembly Definition
Addresses
Default Pointers
Assembly Working
Addresses
Pointer 11 = 1632 & 1633
Alarm 4 Low Set Point
Registers 60 & 61
Registers 220 & 221
Registers 62 & 63
Registers 222 & 223
Registers 64 & 65 Registers 224 & 225
Registers 66 & 67
Registers 226 & 227
Registers 68 & 69
Registers 228 & 229
Registers 70 & 71
Registers 230 & 231
Registers 72 & 73
Registers 232 & 233
Registers 74 & 75
Registers 234 & 235
Registers 76 & 77
Registers 236 & 237
Registers 78 & 79
Registers 238 & 239
Value of Pointer 11
Pointer 12 = 2540 & 2541
Profile Action Request
Value of Pointer 12
Pointer 13 = 2520 & 2521
Profile Start
Value of Pointer 13
Pointer 14 = 1890 & 1891
Heat Proportional Band
Value of Pointer 14
Pointer 15 = 1892 & 1893
Cool Proportional Band
Value of Pointer 15
Pointer 16 = 1894 & 1895
Time Integral
Value of Pointer 16
Pointer 17 = 1896 & 1897
Time Derivative
Value of Pointer 17
Pointer 18 = 1900 & 1901
Heat Hysteresis
Value of Pointer 18
Pointer 19 = 1902 & 1903
Cool Hysteresis
Value of Pointer 19
Pointer 20 = 1898 & 1899
Deadband
Value of Pointer 20
Assembly Definition
Addresses
Default Pointers
Assembly Working
Addresses
Modbus Map 1. These require the user to change the defaults for limit when utilized.