EasyManua.ls Logo

Watlow PM LEGACY PM3 - Page 25

Watlow PM LEGACY PM3
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow PM LEGACY™ Limit Controller 25 Chapter 2 Install and Wire
Warning:
ç
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.
Note:
Maximum wire size termina-
tion and torque rating:
0.0507 to 3.30 mm
2
(30 to
12 AWG) single-wire termi-
nation or two 1.31 mm
2
(16
AWG)
0.56 Nm (5.0 in-lb.) torque
Note:
Adjacent terminals may be
labeled differently, depending
on the model number
.
Note:
To prevent damage to the
controller, do not connect
wires to unused terminals.
Note:
Maintain electrical isolation
between analog input 1, dig-
ital input-outputs, switched
dc/open collector outputs
and process outputs to pre-
vent ground loops.
Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical
relay, solid state relay or
open collector output options
requires use of an R.C. sup-
pressor.
Output 4 Switched DC
dc+
dc-
L3
K3
J3
W4
Y4
T2
S2
R2
Slot B
Maximum open circuit
voltage is 22 to 25V
(dc)
30mA max. per single
output / 40mA max.
total per paired out-
puts (1 & 2, 3 & 4)
Typical drive; 4.5V
(dc) @ 30mA
Short circuit limited to
<50mA
NPN transistor sink
Use dc- and dc+ to
drive external sol-
id-state relay
1-pole DIN-A-MITE: up
to 4 in parallel or 4 in
series
2-pole DIN-A-MITE: up
to 2 in parallel or 2 in
series
3-pole DIN-A-MITE: up
to 2 in series
Output 4:
PM6[L,M] _ _J - _ A _ [C]
G_ _
common
24V
X
_
dc +
dc -
W
_
Y
_

Table of Contents