Watlow PM LEGACY™ Limit Controller 63 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP -
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
Index
Pa-
rame-
ter
ID
Data
Type
and
Ac-
cess
**
A.dL
A.dL
Alarm (1 to 4)
Delay Time
Set the span of time
that the alarm will be
delayed after the pro-
cess value exceeds
the alarm set point.
0 to 9,999 sec-
onds
0 Instance 1
Map 1Map 2
1520 1920
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D
(109)
1 to 4
0x15
(21)
31 9021 uint
RWES
a.CLr
A.Clr
Alarm (1 to 4)
Clear Alarm
Write to this register
to clear an alarm
Note:
If an alarm is setup
to latch when active
a.CLr will appear on
the display.
CLr Clear (0)
ignr Ignore (204)
- - - - Instance 1
Map 1Map 2
1504 1904
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xD (13)
- - - - 9013 uint
W
a.sir
A.Sir
Alarm (1 to 4)
Silence Alarm
Write to this register
to silence an alarm
Note:
If an alarm is setup
to silence alarm
when active a.sir
will appear on the
display.
siL Silence
(1010)
- - - - Instance 1
Map 1Map 2
1506 1906
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xE (14)
- - - - 9014 uint
W
a.st
A.St
Alarm (1 to 4)
Alarm State
Current state of alarm
str Startup (88)
nonE None (61)
bLo Blocked (12)
aL.L Alarm low (8)
aL.h Alarm high
(7)
aL.E Error (28)
- - - - Instance 1
Map 1Map 2
1496 1896
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
9
- - - - 9009 uint
R
** R: Read, W: Write, E: EEPROM, S: User Set