Watlow PM LEGACY™ Limit Controller 82 Chapter 7 Factory Page
Factory Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
In-
stance
Attri-
bute
hex
(dec)
Pro-
fibus
In-
dex
Param-
eter
ID
Data
Type
and Ac-
cess **
ELo.o
ELo.o
Calibration (3)
Electrical Output
Offset
Change this val-
ue to calibrate
the low end of
the output range.
-1,999.000 to
9,999.000
0.0 Instance 3
Map 1Map 2
808 928
0x76
(118)
3
5
- -
- -
18005 float
RWES
ELo.S
ELo.S
Calibration (3)
Electrical Output
Slope
Adjust this value
to calibrate the
slope of the out-
put value.
-1,999.000 to
9,999.000
1.0 Instance 3
Map 1Map 2
810 930
0x76
(118)
3
6
- -
- -
18006 float
RWES
Pn
Pn
Calibration (1 to
2)
Part Number
Displays current
setting for con-
trol model num-
ber.
fCty
Factory
UsEr
User
- - - - - - - - - - - - - -
- -
- - - - uint
R
CodE
CodE
Calibration (1 to
3)
Public Key
Changes the
control to User
or back to origi-
nal model num-
ber as shown on
the side of the
control.
2501
User Settings
606
Factory model
number
4999 - - - - - - - - - - -
-
- - - - uint
RWES