18
Description of Controls and Functions
Touching the icon on the “Programming” Menu will allow access to the sanitization Function:
Item Field Range Default When Displayed Description Additional Info
Temperature 120 to 180ºF 140ºF After PIN correctly entered
The sanitization target
temperature.
Time 0 to 600 mins 60 mins After PIN correctly entered
Countdown starts
once DHW is up to the
Sanitization Temperature
Sanitization Timer.
Mode ON <> OFF OFF After PIN correctly entered Turn sanitization on or off.
The Sanitization Function allows access to the following fields:
Mode
OFF
Temperature
160°F
Time
30 min
Back Up Down
Sanitization
Enter
?