50
USER GUIDE WebdynSunPM
WebdynSunPM User guide Version 1.0
enableReading
Activation of a read request:
0 => activated in instant mode (settings)
1 => activated in polling mode (measurements)
2 => deactivated
enableWriting
Activation of a write request
0 => activated for writing with a review before write action
1 => activated for simple writing
2 => deactivated
option1
Reserved
option2
Reserved
"Modbus_VariablesTables" declarations are shown in the table below. Each element in this
table is defined by 12 fields separated by a semicolon.
Champ
Description
varId
Variable index from 1 to N
indexRequest
Name of the Modbus query set in the table Modbus_RequestsTables
varName
Modbus variable name
type
Variable type inherited from v1
1 => bit field
2 => octet (xINT8)
3 => word (xINT16)
4 => reversed word (xINT16 + byte swap)
5 => double word (xINT32)
6 => reversed double word (xINT32 + word swap)
7 => floating 32 bits
8 => floating 32 bits + word swap
9 => Character string
New variable type
12 => xINT32 + byte swap
13 => xINT64
14 => xINT64 + byte swap
15 => xINT64 + word swap
20 => bit field + byte swap
21 => bit field + word swap
signed
Variable value
1 => signed
2 => unsigned
position
Variable position in the array
1 to N
option1
Reserved
option2
Reserved