CFW-11 | 3-13
Optionally, slow blow fuses can be used at the input. They must be sized for 1.2 x the inverter rated input
current. In this case, the installation is protected against short-circuit, but not the inverter input rectifier. This
may result in major damage to the inverter in the event of an internal component failure.
Table 3.2 - Recommended wire gauge and fuses for standard models - use only copper wire [75 ºC (167 °F)]
Model
Frame Size
Power Terminals
Duty
Cycle
Wiring
Fuse I
2
t
@ 25 ºC
[A
2
s]
WEG Recommended
Fuses FNH aR
Knife Contact
WEG
Recommended
Fuses FNHFE aR
Flush End
Terminals
Bolt
(wrench/bolt
head type)
Recommen-
ded
Torque N.m
(lbf.in)
mm
2
AWG
Terminals
Frame Size
In
[A]
Item SAP
Frame Size
In
[A]
Item SAP
CFW110242T4
F
R/L1 - S/L2 - T/L3 -
U/T1 - V/T2 - W/T3
M12 (Phillips
hex head)
60
(531.00)
HD 2 x 50 2 x 1/0
Ring
tongue
320000 2 450 10824055 3 450 12644962
ND 2 x 70 2 x 1/0
DC+, DC-
(use them
only for braking)
M8 (Phillips
hex head)
10 (88.5) HD/ND 50 1/0