5
HMI
Table 5.1: Required procedure for each kind of action
Action Procedure
Activate password
1. Set P200 with the desired value for the password (P200 = password)
2. The setting is completed, the new password is active and P200 is automatically adjusted for 1
(password active)
(1)
Change password
1. Set the current value of the password (P000 = password)
2. Set the desired value for the new password in P200 (P200 = new password)
3. The setting is completed, the new password is active and P200 is automatically adjusted for 1
(password active)
(1)
Disable password
1. Set the current value of the password (P000 = password)
2. Set inactive password (P200 = 0)
3. The setting is completed, the password is disabled
(2)
Disable password
1. Activate a factory default by means of P204
2. The setting is completed, the password is disabled
(2)
(1) It only allows changing the content of the parameters when P000 is equal to the value of the password.
(2) It is allowed to change the content of the parameters and P000 is inaccessible.
P204 - Load/Save Parameters
Range: 0 to 4 = Not Used
5 = Load 60Hz
6 = Load 50Hz
7 = Load User
8 = Not Used
9 = Save User
10 = Not Used
11 = Load Default SoftPLC
12 to 13 = Reserved
Properties: cfg
Description:
The Table 5.2 on page 5-2 describes the actions performed by each option.
Table 5.2: Option of parameter P204
P204 Action
0 to 4 Not Used: no action
5 Load WEG 60 Hz: it loads the default parameters on the inverter with the factory default for 60 Hz
6 Load WEG 50 Hz: it loads the default parameters on the inverter with the factory default for 50 Hz
7 Load User: it transfers the content of the memory from user parameter to the inverter current parameters
8 Not Used: no action
9 User:
transfers the current content of the parameters to the user’s parameter memory
10 Not Used: no action
11 Load Default SoftPLC: it loads the factory default in SoftPLC parameters (P910 to P959)
12 and 13 Reserved
In order to load the parameters of user for operating area of the inverter (P204 = 7) it is necessary that this area be
previously saved.
The operation of uploading this memory (P204 = 7), can also be done via digital inputs (DIx). For further details
referring to this programming, refer to Section 9.6 DIGITAL INPUTS on page 9-11.
✓
NOTE!
When P204 = 5 or 6, parameters P295 (Inv. Rated Current), P296 (Line Rated Voltage) and P308
(Serial Address) are not changed.