WEG SSW-05 Plus Series - P204 & P215 Parameter Functions

WEG SSW-05 Plus Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENGLISH
Parameter Description / Notes
The keypad copy function is used to transfer the content of the parameters from one
SSW to another.
Note:
The Keypad Copy Function is only available when using HMI-SSW05-RS.
P215
Keypad Copy Function
P215
0
1
2
Notes
-
Transfers the actual parameter values
of the SSW to non volatile memory
(EEPROM) of the HMI-SSW05-RS keypad.
The actual SSW parameters are not
changed.
Transfers the content of the non volatile
memory of the keypad (EEPROM) to the
SSW parameters.
Action
Off
Procedure is as follows:
1. Connect the keypad (HMI-SSW05-RS) to the SSW from which the parameters willl be
copied (SSW A - source SSW).
2. Set P215=1 (copy) to transfer the parameter values from the SSW A to the keypad.
Press key. During running of the Copy Function, display will show .
P215 resets automatically to 0 (Off) after transfer has been completed.
3. Disconnect the keypad from the SSW (A).
4. Connect the same keypad to the SSW to which the parameters will be transferred
(SSW B - target SSW).
5. Set P215=2 (paste) to transfer the content of the of the keypad (EEPROM has the
SSW A parameters) to SSW B.
Press the key. While the keypad is running the paste function, the display shows
, an abbreviation for paste. When P215 returns to 0, the parameter
transfer has been concluded. Now SSWs A and B will have the same parameter
values.
To copy the parameter content of the SSW A to other SSW(s), repeat steps 4 to 5 above.
Copy
(SSW keypad)
Paste
(keypadSSW)
Figure 22.2 - Copying the parameters from the SSW A to the SSW B, by using the Copy Function
and the HMI-SSW05-RS keypad.
Parameters
Parameters
EEPROM
Soft-Starter
A
SSWHMI (Copy)
P215 = 1
Press
HMI-SSW05-RS
Soft-Starter
B
EEPROM
HMI-SSW05-RS
HMISSW (Paste)
P215 = 2
Press
Programs all parameters to the standard factory default, when P204=5.
The parameters P000 and P295 are not changed when the factory default parameters
are loaded through P204=5.
P204
Load Factory Setting
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com