23. APPENDIX FOR CE CONFORMANCE:
The SSW-05 Plus, was tested to meet the following directives:
23.1. EMC and LVD Directives:
EMC Directive 89/336/EEC (Electromagnetic Compatibility), using a Technical Construction File and the following
standards:
EN60947-4-2: Low-voltage switchgear and controlgear Part 4, contactors and motor-starters Section 2. AC
semiconductor motor controllers and starters.
Low Voltage Directive (LVD) 73/23/EEC
ATTENTION!
The SSW-05 Plus line has been designed for class A equipment. Use of the products in domestic environments may
cause radio interference, in which case the user may be required to employ additional mitigation methods.
Note:
The conformity of the Soft-Starter to any standard does not guarantee that the entire installation will conform.
Many other factors can influence the total installation. Only direct measurements can verify total conformity.
23.2. Requirements for Conforming Installations:
23.2.1. EMC Directive:
The following items are required for CE conformance:
1. The Soft-Starters must be installed into closed metallic boxes or panels that have a door only able to be
opened with a tool. A suitable cooling must be provided to ensure that the temperature will be within the allowed
range.
23.2.2. Low Voltage Directive (LVD):
The following items are required for CE conformance:
1. The same as item 1 above.
2. The installation must provide a supply disconnecting (isolation) device. A hand-operated supply disconnecting
device must be provided for each income supply and be near to the equipment. This device must disconnect
the Soft-Starter from the supply when required (e. g. during work on the eletrical equipment). See EN60204-1, 5.3.
Specify the current and voltage of this disconnecting device according to the data given in the item 6.
DANGER!
This equipment must not be used as an emergency stop mechanism (See EN60204, 9.2.5.4).
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WEG SSW-05 Plus Series and is the answer not in the manual?

WEG SSW-05 Plus Series Specifications

General IconGeneral
BrandWEG
ModelSSW-05 Plus Series
CategoryController
LanguageEnglish

Related product manuals