Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014 Page 149
Output 7 Retransmit Input 2 Maximum Value For Loop 2 Retransmit Maximum
Dec 2461 18845 37690
RW
Displayed value at which the retransmission output reaches its
maximum level (e.g. 2mA if type is 4-20mA).
Adjustable from -9999 to 9999.9
Hex 099D 499D 933A
Loop 1 Setpoint Parameters
Parameter Name & Register Address
Integer Int +1 Float Access Values & Descriptions
Loop 1 Setpoint Minimum Minimum Allowed Setpoint For Loop 1
Dec 3944 20328 40656
RW
Valid between the scaled input lower & upper limits
Hex 0F68 4F68 9ED0
Loop 1 Setpoint Maximum Maximum Allowed Setpoint For Loop 1
Dec 3945 20329 40658
RW
Valid between the scaled input lower & upper limits
Hex 0F69 4F69 9ED2
Loop 1 Main Local Setpoint Value Main Setpoint Value For Loop 1
Dec 3960 20344 40688
RW
Valid between Setpoint Maximum and Minimum
Hex 0F78 4F78 9EF0
Loop 1 Main Local Setpoint Offset Offset Of Main Setpoint Of Loop 1
Dec 3961 20345 40690
RW
Changes effective setpoint (for multi-zone slaves. +ve values
added -ve values subtracted.
Setpoint always limited by Setpoint Max and Min.
Hex 0F79 4F79 9EF2
Loop 1 Alternate Local Setpoint Value Alternate Setpoint Value For Loop 1
Dec 3962 20346 40692
RW
Valid between Setpoint Maximum and Minimum
Hex 0F7A 4F7A 9EF4
Loop 1 Alternate Local Setpoint Offset Offset Of Alternate setpoint Of Loop 1
Dec 3963 20347 40694
RW
Changes effective setpoint (for multi-zone slaves. +ve values
added -ve values subtracted.
Setpoint always limited by Setpoint Max and Min.
Hex 0F7B 4F7B 9EF6
Loop 1 Main Setpoint Source Value Main Setpoint Source For Loop 1
Dec 4050 20434 40868
RW
0 Local Setpoint 1
Hex 0FD2 4FD2 9FA4
1 Not Used
Loop 1 Alternate Setpoint Source Value Alternate Setpoint Source For Loop 1
Dec 4051 20435 40870
RW
0 Not Used
Hex 0FD3 4FD3 9FA6
1 Local Setpoint 2
2 Input 2 Remote Setpoint
3 Input A Remote Setpoint
Loop 1 Setpoint Select Value Setpoint Select For Loop 1
Dec 4122 20506 41012
RW
0 Main Setpoint
Hex 101A 501A A034
1 Alternate setpoint
Loop 1 Setpoint Ramp Rate Setpoint Ramp Rate For Loop 1
Dec 4123 20507 41014
RW
0 to 10000 display units per hour
(1 to 9999 is ramp rate per hour, either 0 or >10000 = Off)
Hex 101B 501B A036
Loop 1 Target Setpoint Actual Setpoint Value Of Selected Loop 1 Setpoint
Dec 4125 20509 41018
RO
The Loop 1 target setpoint value when ramping
Hex 101D 501D A03A
Operator Access Setpoint Ramp Rate Value Operator Access To Loop 1 Setpoint Ramp Rate
Dec 4126 20510 41020
RW
0 No
Hex 101E 501E A03C
1 Yes