EasyManua.ls Logo

West Control Solutions Pro-EC44 - Supervisor Mode

West Control Solutions Pro-EC44
272 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014 Page 38
 Cascade Control: Normal Operation
LED Indicators
LED Function Labels
Cascade Status
Master Process Value
Slave Process Value
Master Setpoint (
Slave SP if
Cascade Open)
Control Deviation (±5% of
span) & Power Graphs
CASCADE CONTROL
Default LED indicator functions are PRI, SEC, TUNE & ALARM - the functions and their labels can be
altered only with the PC configuration software.
Cascade Status shows “Cascade” when cascade is operating normally and “Cascade Open” when
the master / slave link has been disconnected. Master & Slave Process Values.
In valve motor drive mode, the power bar-graph is replaced by valve Open / Stop / Close.
In manual mode the slave setpoint is replaced by the %Manual Power and the label “MAN”.
In manual mode with valve motor drive the slave setpoint is replaced by valve Open / Stop / Close.
If control is disabled the effective master setpoint value is replaced byOFF”.
 Ratio Control: Normal Operation
LED Indicators
LED Function Labels
Relative Process Value
Ratio & Setpoint Labels
Relative Setpoint
Control Deviation (±5% of
span) & Power Graphs
RATIO CONTROL
Default LED indicator functions are PRI, SEC, TUNE & ALARM - the functions and their labels can be
altered only with the PC configuration software.
In manual mode the ratio setpoint value is replaced by the %Manual Power and the labelMAN”.
If control is disabled the effective setpoint value is replaced by “OFF”.
Operator Profile
Control
Allows the operator to control the defined profiles.
If a profile is running, the choices are: Do Nothing; Abort Profile (end
immediately); Jump to Next Segment; Hold Profile or Release Hold.
If no profile is running, the choices are: Do Nothing; Run Profile; End Profile
Control (returns to standard controller operation) or Select Profile.
◘ only shown if set to do so in Display Configuration.
 Single Control Loop: Profiler Status
LED Indicators
LED Function Labels
Process Value & Setpoint
Engineering Units
Profile Name & Progress
Segment No, Type &
Progress (or Delayed Start
Time)
Profile Status Indicator:
► Run, ▌▌ Held, Stopped
1-LOOP PROFILE STATUS
Default LED indicator functions are as shown in the initial base screen.
In manual mode the effective setpoint is replaced by the %Manual Power and the label “MAN”.
In manual mode with valve motor drive the setpoint is replaced by valve Open / Stop / Close.
If control is disabled the effective setpoint value is replaced by “OFF”.
Note: If power is lost when a profile is running and recovery is set to continue,
the bar-graph re-starts from the beginning but the overall time remains correct.

Table of Contents