EasyManua.ls Logo

West Control Solutions Pro-EC44 - Connection from PC to Bottom Configuration Socket; Connection from PC to Rear RS485 Communications Option

West Control Solutions Pro-EC44
272 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014 Page 237
A communications settings screen is shown whenever the user attempts to connect to the
instrument from the software. If the settings are not in-line with the information below, the
software may not be able to communicate with the instrument.
Connection from PC to Bottom Configuration Socket
When using the built-in configuration socket, set the communications parameters as shown
here and in the following table.
Device connector = Configuration Socket
PC connector = the PC Serial Com port number you are connected to
Start and Stop bits = 1
Data bits = 8.
Parity, Bit Rate & Address = must match settings in the table below
Connection from PC to Rear RS485 Communications Option
When using the optional RS485 communications, set the parameters as shown here.
Device connector = Bus
PC connector = the PC Serial Com port number you are connected to
Start and Stop bits = 1
Data bits = 8
Parity, Bit Rate & Address = must match the settings in the instruments own
Communication Configuration menu.
Note: When uploading or downloading via the bottom mounted configuration
port, the required software communication settings depend on the module fitted
in slot A. See the table below.
Slot A Module Bit Rate Parity Address
Slot A Empty 19200 None 1
Digital Input 19200 None 1
Ethernet
Comms
9600 None 1
Auxiliary Input 4800 None 1
RS485
Comms
Must match the Communication
Configuration menu settings.

Table of Contents