Pro-EC44 2-Loop Graphical Profile Controller & Recorder
Pro-EC44 Product Manual - 59540-2 September 2014 Page 186
Operator Access To Profile Control Value Profile Control From Operation Mode
Dec 8260 24644 49288
RW
0 Operation Mode profile control disabled
Hex 2044 6044 C088
1 Operation Mode profile control enabled
Profile Cycles Run Profile Cycles Run Status
Dec 8247 24631 49262
RO
The Number of times the currently running profile has cycled
Hex 2037 6037 C06E
Event 1 Status Value Status Of Event 1
Dec 8249 24633 49266
RO
0 Event 1 Inactive
Hex 2039 6039 C072
1 Event 1 Active
Event 2 Status Value Status Of Event 2
Dec 8250 24634 49268
RO
0 Event 2 Inactive
Hex 203A 603A C074
1 Event 2 Active
Event 3 Status Value Status Of Event 3
Dec 8251 24635 49270
RO
0 Event 3 Inactive
Hex 203B 603B C076
1 Event 3 Active
Event 4 Status Value Status Of Event 4
Dec 8252 24636 49272
RO
0 Event 4 Inactive
Hex 203C 603C C078
1 Event 4 Active
Event 5 Status Value Status Of Event 5
Dec 8253 24637 49274
RO
0 Event 5 Inactive
Hex 203D 603D C07A
1 Event 5 Active
Segment Type Status Value The Current Running Profile Segment Type
Dec 8258 24642 49284
RO
0 No segment
Hex 2042 6042 C084
1 Setpoint ramping up
2 Step
3 Dwell
4 Held
5 Loop
6 Join
7 End
8 Setpoint ramping down
Active Profile Name Name of Currently Selected Profile
Dec 8259 24643 49286
RO
The name of the currently selected profile
Hex 2043 6043 C086
Secondary Profile Status Value Secondary Profile Status of Selected Profile
Dec 8232 24616 49232
RO
0 Profile running
Hex 2028 6028 C050
1 Input sensor break
2 Profile not valid
3 Controller in manual mode
4 Profile finished and maintaining last profile setpoint
5 Profile finished with control outputs off
6 Profile control has ended. Unit is Controller Mode.
Delay time Remaining Profile Delay Time
Dec 8233 24617 49234
RO
The current start delay time remaining in seconds, before
selected profile will begin.
Hex 2029 6029 C052