Installation and operating instructions Wilo-Control EC-L 65
6.5.2 Switchgear mains connection
CAUTION
Material damage due to incorrectly set mains voltage!
The switchgear can be operated at different mains voltages. The mains voltage is set
to 400V at the factory. To use another mains voltage, change the position of the
cable jumper before connection. If the wrong mains voltage is set, the switchgear
will be destroyed!
Insert the connection cable laid by the customer through the threaded cable connec-
tions and secure. Connect the wires to the terminal strip according to the connection
diagram.
L1 L2
3~380-400 V
50/60 Hz
L
1~230 V
50/60 Hz
L3
N
com
230
380
400
1
2
3
Fig.4: Mains connection, Wilo-Control EC-L
1.../EC-L 2...
1 Terminal strip: Mains connection
2 Adjustment mains voltage
3 Terminal strip: Earth (PE)
Mains connection 1~230V:
Cable: 3-core
Wire: L, N, PE
Adjustment mains voltage: Converter bridge 230/COM
Mains connection 3~380V:
Cable: 4-core
Wire: L1, L2, L3, PE
Adjustment mains voltage: Converter bridge 380/COM
Mains connection 3~400V:
Cable: 4-core
Wire: L1, L2, L3, PE
Adjustment mains voltage: Converter bridge 400/COM (factory setting)
PE
1 ON
L1
L3
L2
T1
T3
T2
0
OFF
3
2
1
L1 L2
3~380-400 V
50/60 Hz
L
1~230 V
50/60 Hz
L3
N
com
230
380
400
Fig.5: Mains connection, Wilo-Control EC-L
3...
1 Main switch
2 Adjustment mains voltage
3 Terminal strip: Earth (PE)
6.5.3 Mains connection, pump
NOTICE
Rotating field, power supply and pump connection
The rotating field is routed from the mains connection directly to the pump connec-
tion. Check the required rotating field of the pumps to be connected (clockwise or
counter-clockwise)! Observe the installation and operating instructions of the
pumps.