en Commissioning
84 WILO SE 2018-12
Fig.53: Menu 5.68
Menu no. 5.68
Description Mains connection rotating field monitoring On/Off
Value range on, off
Factory setting on
NOTICE!Switch off during alternating current connection!
Fig.54: Menu 5.69
Menu no. 5.69
Description Motor current monitoring On/Off
Value range on, off
Factory setting on
NOTICE!Switch off during alternating current connection!
Fig.55: Menu 5.70
Menu no. 5.70
Description Max. switching frequency per hour, per pump
Value range 0 … 60
Factory setting 0
Explanation
If the max. number of starts has been exceeded, the col-
lective fault signal (SSM) is activated. Value “0” = function
deactivated.
Menu 1: Values for switching on and off
*NOTICE!The menu items 1.12 to 1.17 are only visible if, in menu 5.07, the value
“Level” or “Bell” have been set.
**NOTICE!The actual value range is dependent on the setting in menu 5.09.
Fig.56: Menu 1.09
Menu no. 1.09
Description Base-load pump switch-off delay
Value range 0…60s
Factory setting 0s
Fig.57: Menu 1.10
Menu no. 1.10
Description Activation delay, peak-load pump
Value range 0…30s
Factory setting 3s
Fig.58: Menu 1.11
Menu no. 1.11
Description Switch-off delay peak-load pump
Value range 0…30s
Factory setting 1s