Commissioning en
Installation and operating instructions Wilo-Control EC-L 85
Fig.59: Menu 1.12
Menu no. 1.12*
Description Base-load pump On level
Value range** 0.06…12.5m
Factory setting 0.40m
Explanation
Operating mode “drain”: Value must be 0.03m higher than
the “Base-load pump Off level” (menu 1.13).
Operating mode “fill”: Value must be 0.03m lower than the
“Base-load pump Off level” (menu 1.13).
Fig.60: Menu 1.13
Menu no. 1.13*
Description Base-load pump Off level
Value range** 0.06…12.5m
Factory setting 0.23m
Explanation
Operating mode “drain”: Value must be 0.03m lower than
the “Base-load pump On” level (menu 1.12).
Operating mode “fill”: Value mandatory 0.03m higher than
the “Base-load pump On level” (menu 1.12).
Fig.61: Menu 1.14
Menu no. 1.14*
Description Level peak-load pump1 on
Value range** 0.06…12.5m
Factory setting 0.42m
Explanation
Operating mode “drain”: The value must be 0.03m higher
than the “Peak-load pump 1 On” level (menu 1.15). The
switch-on level must be greater than/equal to the switch-
on level of the base-load pump (menu 1.12).
Operating mode “fill”: The value must be 0.03m lower than
the “Peak-load pump 1 Off” level (menu 1.15). The switch-
on level must be lower than/equal to the switch-on level
of the base-load pump (menu 1.12).
Fig.62: Menu 1.15
Menu no. 1.15*
Description Peak-load pump 1 Off level
Value range** 0.06…12.5m
Factory setting 0.25m
Explanation
Operating mode “drain”: Value mandatory 0.03m lower
than the “Peak-load pump 1 On” level (menu 1.14). The
switch-off level must be greater than/equal to the switch-
on level of the base-load pump (menu 1.13).
Operating mode “fill”: Value must be 0.03m higher than
the “Peak-load pump 1 On” level (menu 1.14). The switch-
off level must be lower than/equal to the switch-off level
of the base-load pump (menu 1.13).
Fig.63: Menu 1.16
Menu no. 1.16*
Description Peak-load pump 2 On level
Value range** 0.06…12.5m
Factory setting 0.42m
Explanation
Operating mode “drain”: The value must be 0.03m higher
than the “Peak-load pump 2 Off” level (menu 1.17). The
switch-on level must be greater than/equal to the switch-
on level of the peak-load pump (menu 1.14).
Operating mode “fill”: The value must be 0.03m lower than
the “Peak-load pump 2 Off” level (menu 1.17). The switch-
on level must be lower than/equal to the switch-on level
of the peak-load pump (menu 1.14).