EGCP-2 Engine Generator Control Package Manual 26174
210 Woodward
Item: Range: Default:
A
s Set Value: Note:
REVERSE PWR
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Soft Shutdown
REVERSE kVAR
LIMIT
Min: –100.0
Max: –5.0
-50.0%
REVERSE kVAR
DELAY
Min: 0.1
Max: 5.0
5.0 s
REVERSE kVAR
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
REMOTE FAULT1 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
FAULT1 TIMER Min: 0.0
Max: 30.0
0.0 s
REMFLT 1
STABLE DLY
Enabled
Disabled
Enabled Enabled = 15 Second
Delay
REMOTE FAULT2 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
FAULT2 TIMER Min: 0.0
Max: 30.0
0.0 s
REMFLT 2
STABLE DLY
Enabled
Disabled
Enabled Enabled = 15 Second
Delay
REMOTE FAULT3 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Hard Shutdown
FAULT3 TIMER Min: 0.0
Max: 30.0
0.0 s
REMOTE FAULT4 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
FAULT4 TIMER Min: 0.0
Max: 30.0
0.0 s
REMOTE FAULT5 Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
FAULT5 TIMER Min: 0.0
Max: 30.0
0.0 s