EasyManua.ls Logo

Worcester GB162-100

Worcester GB162-100
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Display information
6720813171 (2015/04)56
e
[2/y/\|
e
[2/8/2|
e
Fault:
No feedback from the pump.
No Off
e
[3/a/\|
e
[2/6/4|
e
Fault:
The tacho signal from the fan has failed during the
operating phase.
No
4)
5)
Off
e
[3/c/\|
e
[2/1/7|
e
Fault:
No current of air after a certain time.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[3/f/\|
e
[2/7/3|
e
Operating phase:
The appliance has been switched off for a couple of
seconds, because it had been running without any
interruption for 24 hours. This is a safety check.
No
4)
5)
Off
e
[3/l/\|
e
[2/1/4|
e
Fault:
The tacho signal from the fan is not present during the
pre-operative or operating phase.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[3/p/\|
e
[2/1/6|
e
Fault:
The fan is running too slowly.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[3/y/\|
e
[2/1/5|
e
Fault:
The fan is running too fast.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/a/\|
e
[2/1/8|
e
Fault:
The flow temperature sensor has detected a flow
temperature of over 105 °C.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/c/\|
e
[2/2/4|
e
Fault:
There is no bridging cable between contacts 22 and 24 of
the UBA 3 contact strip.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/e/\|
e
[2/7/8|
e
Fault:
The sensor test has failed.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/f/\|
e
[2/1/9|
e
Fault:
The safety temperature sensor has detected a flow
temperature of over 105 °C.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/l/\|
e
[2/2/0|
e
Fault:
The contacts for the safety temperature sensor have
shorted or the safety temperature sensor has detected a
flow temperature of over 130 °C.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/p/\|
e
[2/2/1|
e
Fault:
The contacts for the safety temperature sensor have
shorted.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/u/\|
e
[2/2/2|
e
Fault:
The contacts for the safety temperature sensor have been
interrupted.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[4/y/\|
e
[2/2/3|
e
Fault:
The contacts for the safety temperature sensor have been
interrupted.
Yes
5)
6)
7)
8)
flashing
1Hz
No heating operation and no
DHW.
e
[5/h/\|
e
[2/6/8|
e
Operating phase:
Component test phase.
No Off
e
[6/a/\|
e
[2/2/7|
e
Fault:
The system has detected an insufficient ionisation current
during the ignition phase.
No
4)
5)
Off
Display codes
Display code
LED on
UBA 3 Other effectsz
Main
display
code
z
Sub
display
code
z Key to display code
Reset
requi-
red?
Table 24 Display codes

Table of Contents

Other manuals for Worcester GB162-100