Calibration
Remote Interface Calibration Procedure
Release 3.0 191
Analog
Programming
Interface
0-10V Range
The 0-10V range of the analog programming interface must be calibrated separately.
Follow the procedure exactly as for calibrating the 0-5V range, except that all the
analog signals will be scaled by a factor of 2.
The commands will begin with the header:
CAL:ANAL:10V:...
The inputs to the programming lines should be approximately 1V for the minimum
calibration level and 9V for the maximum calibration level.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com