Parameter List
1
1.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 125
No. Name Range Unit
Control Method (A1-02 Setting)
V/f
(0)
OLV
(2)
E1-04
Maximum Output
Frequency
40.0 - 400.0
*2 *3
0.1 Hz 60.0
*4
60.0
E1-05 Maximum Output Voltage 0.0 - 255.0
*5
0.1 V 200.0
*4
200.0
E1-06 Base Frequency 0.0 - 400.0
*3
0.1 Hz 60.0
*4
60.0
E1-07 Mid Point A Frequency 0.0 - 400.0
*3
0.1 Hz 3.0
*4
3.0
E1-08 Mid Point A Voltage 0.0 - 255.0
*5
0.1 V 15.0
*4
11.0
E1-09
Minimum Output
Frequency
0.0 - 400.0
*3
0.1 Hz 1.5
*4
0.5
E1-10 Minimum Output Voltage 0.0 - 255.0
*5
0.1 V 9.0
*4
2.0
F1-09
Overspeed Detection Delay
Time
0.0 - 2.0 0.1 s - -
L1-01
Motor Overload (oL1)
Protection
0 - 4 1 2 2
L2-31
KEB Start Voltage Offset
Level
0 - 100
*5
1 V 0 0
L3-05
Stall Prevention during
RUN
0 - 3 1 1 1
L3-20
DC Bus Voltage Adjustment
Gain
0.00 - 5.00 0.01 1.00 0.30
L3-21
OVSuppression Accel/
Decel P Gain
0.10 - 10.00 0.01 1.00 1.00
L3-36
Current Suppression
Gain@Accel
0.0 - 100.0 0.1 10.0 20.0
L4-01
Speed Agree Detection
Level
0.0 - 400.0
*6
0.1 0.0 Hz 0.0 Hz
L4-02
Speed Agree Detection
Width
0.0 - 20.0 0.1 2.0 Hz 2.0 Hz
L4-03
Speed Agree Detection
Level(+/-)
-400.0 - +400.0
*7
0.1 0.0 Hz 0.0 Hz
L4-04
Speed Agree Detection
Width(+/-)
0.0 - 20.0 0.1 2.0 Hz 2.0 Hz
L8-40
Carrier Freq Reduction Off-
Delay
0.00 - 2.00 0.01 s 0.50 0.50
L8-90
STPo Detection Level (Low
Speed)
0 - 5000 1 - -
n5-04 Speed Response Frequency 0.00 - 500.00 0.00 Hz - -
n8-35
Initial Pole Detection
Method
0 - 2 1 - -
n8-51
Pull-in Current @
Acceleration
0 - 200% 1 0 0
o1-03
Frequency Display Unit
Selection
0 - 3 1 0 0
o1-04 V/f Pattern Display Unit 0 - 1 1 - -
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
*2 The default setting changes when the setting of C6-01 [Normal / Heavy Duty Selection] changes.
*3 The setting range changes when the setting of E5-01 [PM Motor Code Selection] changes when A1-02 = 5 [OLV/PM].
*4 The default setting changes when the drive model and E1-03 [V/f Pattern Selection] change.
*5 This is the value for 200 V class drives. Double the value for 400 V class drives.
*6 When A1-02 = 5 [OLV/PM], the maximum value of the setting range is 100.0.
*7 When A1-02 = 5 [OLV/PM], the setting range is -100.0 to +100.0.