1.21 Defaults by Drive Model and Duty Rating ND/HD
132 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
No.
*1
Name Unit Default
- Drive Model - B010 B012 B018
C6-01
Normal / Heavy
Duty Selection
-
HD ND HD ND HD ND
0 1 0 1 0 1
o2-04
Drive Model
(KVA) Selection
Hex. 34 35 37
E2-11
(E4-11, E5-02)
Motor Rated
Power
kW 1.5 2.2 2.2 3.0 3.7 5.5
E2-02
(E4-02)
Motor Rated Slip Hz 2.6 2.9 2.9 2.7 2.73 1.5
E2-03
(E4-03)
Motor No-Load
Current
A 2.8 3 3 3.7 4.5 5.1
E2-05
(E4-05)
Motor Line-to-
Line Resistance
Ω 1.997 1.601 1.601 1.034 0.771 0.399
E2-06
(E4-06)
Motor Leakage
Inductance
% 18.5 18.4 18.4 19 19.6 18.2
E2-10
(E4-10)
Motor Iron Loss W 53 77 77 91 112 172
E5-01
PM Motor Code
Selection
- FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Power Loss Ride
Through Time
s 0.3 0.3 0.5 0.5 1 1
L2-03
Minimum
Baseblock Time
s 0.4 0.5 0.5 0.5 0.6 0.7
L2-04
Powerloss V/f
Recovery Ramp
Time
s 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 160 160 160 160 160 160
L3-02
Stall Prevent
Level during
Accel
% 150 120 150 120 150 120
L3-06
Stall Prevent
Level during Run
% 150 120 150 120 150 120
L3-24
Motor Accel Time
@ Rated Torque
s 0.166 0.145 0.145 0.145 0.154 0.168
L8-02
Overheat Alarm
Level
°C 105 105 110 110 115 115
L8-09
Output Ground
Fault Detection
- 0 0 0 0 0 0
n1-03
Hunting
Prevention Time
Constant
ms 10 10 10 10 10 10
n3-02
HSB Current
Limit Level
% 150 120 150 120 150 120
n5-02
Motor Inertia
Acceleration Time
s 0.166 0.145 0.145 0.145 0.154 0.168
*1 Parameters within parentheses are for motor 2.