Parameter Details
2
2.2 A: Initialization Parameters
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 149
5. Push or to show [A1-02], then push .
The keypad shows the setting value for [A1-02].
6. Push or to make sure that you can change the setting value.
Push (Back) until the keypad shows the Parameter Setup Mode screen.
A1-05: Password Setting
No.
(Hex.)
Name Description
Default
(Range)
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. Enter the correct
password in A1-04 [Password] to unlock parameters and accept changes.
0000
(0000 - 9999)
This parameter locks these parameters:
A1-01 [Access Level Selection]
A1-02 [Control Method Selection]
A1-03 [Initialize Parameters]
A1-06 [Application Preset]
A1-07 [DriveWorksEZ Function Selection]
A2-01 to A2-32 [User Parameter 1 to 32]
Note:
Usually, the keypad will not show A1-05. To show and set A1-05, show A1-04 [Password] and then push and on the keypad at
the same time.
After you set A1-05, the keypad will not show it again until you enter the correct password in A1-04. Make sure that you remember the A1-
05 setting value. If you do not know the A1-05 setting value, contact Yaskawa or your nearest sales representative.
When A1-03 = 2220, 3330 [2-Wire Initialization, 3-Wire Initialization], the drive is initialized to A1-05 = 0000. Be sure to set the password
again when a password is necessary for the application.
Change the setting value in A1-05 to change the password. The new setting value becomes the new password.
When you use the password to unlock and change a parameter, enter a value other than the password in A1-04 to lock the parameter again
with the same password.
If A1-04 A1-05, MEMOBUS Communication cannot read or write A1-05.
A1-06: Application Preset
WARNING! Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06 0), it changes the I/O terminal functions for the
drive and it can cause equipment to operate unusually. This can cause serious injury or death.
No.
(Hex.)
Name Description
Default
(Range)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0
(0 - 5, 8)
The drive software contains the application presets shown below. Set A1-06 to align with the application to let the
drive automatically set the best parameter settings for the selected application. The drive saves parameters that you
frequently use the application in parameters A2-01 to A2-16 [User Parameters 1 to 16] for easy configuration and
reference in Setup Mode.
Water supply pump
Conveyor
Exhaust fan
HVAC fan
Air compressor
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV