EasyManua.ls Logo

YASKAWA GA500 GA50U Series - Page 150

YASKAWA GA500 GA50U Series
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.2 A: Initialization Parameters
150 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Note:
Before you set A1-06, make sure that you set A1-03 = 2220, 3330 [Initialize Parameters = 2-Wire Initialization, 3-Wire Initialization] to
initialize parameters.
It is not possible to change the A1-06 value. To set an application preset, set A1-03 = 2220 to initialize parameters, then set this parameter.
If initializing all parameters will cause a problem, do not change the settings.
If you set A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms] to set parameters to A2-17 to A2-32 [User
Parameters 17 to 32] automatically, the drive will reset these parameters when you change the A1-06 setting.
0 : General-purpose
The drive saves the parameters in Table 2.3 as User Parameters.
Table 2.3 Parameters Saved as User Parameters with the General-purpose Preset
User Parameter No. Parameter No. Saved Name
A2-01
A1-02 Control Method Selection
A2-02
b1-01 Frequency Reference Selection 1
A2-03
b1-02 Run Command Selection 1
A2-04
b1-03 Stopping Method Selection
A2-05
C1-01 Acceleration Time 1
A2-06
C1-02 Deceleration Time 1
A2-07
C6-01 Normal / Heavy Duty Selection
A2-08
C6-02 Carrier Frequency Selection
A2-09
d1-01 Reference 1
A2-10
d1-02 Reference 2
A2-11
d1-03 Reference 3
A2-12
d1-04 Reference 4
A2-13
d1-17 Jog Reference
A2-14
E1-01 Input AC Supply Voltage
A2-15
E1-03 V/f Pattern Selection
A2-16
E1-04 Maximum Output Frequency
A2-17 E1-05 Maximum Output Voltage
A2-18 E1-06 Base Frequency
A2-19 E1-09 Minimum Output Frequency
A2-20 E1-13 Base Voltage
A2-21 E2-01 Motor Rated Current (FLA)
A2-22 E2-04 Motor Pole Count
A2-23 E2-11 Motor Rated Power
A2-24 H4-02 Terminal AM Analog Output Gain
A2-25 L1-01 Motor Overload (oL1) Protection
A2-26 L3-04 Stall Prevention during Decel
1 : Water Supply Pump 2
The drive automatically sets the parameters in Table 2.4 for a water supply pump application.
Table 2.4 Best Parameter Settings for Water Supply Pump Applications
No. Name Optimal Value
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Disabled
C1-01 Acceleration Time 1 1.0 s
C1-02 Deceleration Time 1 1.0 s

Table of Contents

Related product manuals