EasyManua.ls Logo

YASKAWA GA500 GA50U Series

YASKAWA GA500 GA50U Series
524 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
2
2.7 F: Options
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 267
F6-16
[Gateway Mode]
H5-01
[Drive Node
Address]
*1
H5-02
[Communication
Speed Selection]
H5-03
[Communication
Parity Selection]
H5-06
[Drive Transmit
Wait Time]
H5-09
[CE Detection
Time]
b1-01
[Frequency
Reference
Selection 1]
b1-02
[Run Command
Selection 1]
Drive 2
(Slave Drive)
0 02
*3 *4 *5
5 ms (Default)
*6
0.9 s
*7
2 [Memobus/Modbus
Communications]
*8
2 [Memobus/Modbus
Communications]
*8
Drive 3
(Slave Drive)
0 03
*3 *4 *5
5 ms (Default)
*6
0.9 s
*7
2 [Memobus/Modbus
Communications]
*8
2 [Memobus/Modbus
Communications]
*8
Drive 4
(Slave Drive)
0 04
*3 *4 *5
5 ms (Default)
*6
0.9 s
*7
2 [Memobus/Modbus
Communications]
*8
2 [Memobus/Modbus
Communications]
*8
*1 Re-energize the drive to apply the new settings.
*2 Specify the number of slave drives you will connect.
*3 Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
*4 Set a slave address that is different from other slave devices.
*5 Enter the same value that you use for the master drive.
*6 To correctly detect the response timeout, do not change the value of H5-06 from the default value.
*7 Set H5-09 0.9. When H5-09 < 0.9, the drive will detect CE [Modbus Communication Error] before it detects a response timeout.
*8 On each slave drive, set b1-01 [Frequency Reference Selection 1] and b1-02 [Run Command Selection 1] to 2 [Memobus/Modbus
Communications].
An Overview of Gateway Mode
When in gateway mode, the drive will operate as shown in Table 2.42.
A - Controller
B - Communication option
C - Master Drive (Drive 0)
D - Slave Drives (Drives 1 to 4)
Table 2.42 Operation in Gateway Mode
Controller to Communication Option Communication Option to Master Drive (Drive 0)
Master Drive (Drive 0) to Slave Drives (Drives 1 to
4)
The controller and card communicate in the format of
each field bus communications protocol.
Drive 0 sends commands and monitors through normal
field bus communications.
The special registers of Drive 0 use read and write to
send commands to and monitor Drives 1 to 4.
Field bus communication data is written to and read from
the special registers of Drive 0.
Uses MEMOBUS communications.
Drive 0 sends data from its special registers to Drives 1
to 4.
Note:
Energize the slave drive before you energize the master drive. If you energize the master drive first, the drive detects CE [Modbus
Communication Error].

Table of Contents

Related product manuals