2.8 H: Terminal Function Selection
292 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Note:
To input the Run command, activate the terminal for 1 ms minimum.
The default setting for b1-17 [Run Command at Power Up] is 0 [Disregard existing RUN command]. If you enable the Run command on an
energized drive, the protective function activates and the flashes quickly. When the application will let an energized drive Run, set
b1-17 = 1 [Accept Existing RUN Command].
1: LOCAL/REMOTE Selection
Setting Value Function Description
1 LOCAL/REMOTE Selection
Sets drive control for the keypad (LOCAL) or an external source (REMOTE).
Note:
When the MFDI terminal sets the LOCAL/REMOTE selection, on the keypad is disabled.
When LOCAL Mode is selected, the green light for comes on.
When the Run command is ON, you cannot switch between LOCAL Mode and REMOTE Mode.
ON : LOCAL
The keypad is the Frequency reference source and Run command source.
OFF : REMOTE
The frequency reference and Run command settings are set in b1-01, b1-02 [Frequency Reference Selection 1/2] or
b1-15, b1-16 [Run Command Selection 1/2].
2: External Reference 1/2 Selection
Setting Value Function Description
2 External Reference 1/2
Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in REMOTE Mode.
Note:
The ability to switch the Run command source and frequency reference source depends on the setting of b1-07 [LOCAL/REMOTE Run
Selection].
Table 2.47 Ability to Switch the Run Command Source and Frequency Reference Source when Inputting the Run
Command
b1-07 Run command source Frequency reference source
0 [Disregard Existing RUN Command] (Default) No Yes
1 [Accept Existing RUN Command] Yes Yes
ON : b1-15 [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF : b1-01 [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
3: Multi-Step Speed Reference 1
Setting Value Function Description
3 Multi-Step Speed Reference
1
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
Note:
Refer to Setting Procedures for Multi-step Speed Operation on page 225 for more information.
4: Multi-Step Speed Reference 2
Setting Value Function Description
4 Multi-Step Speed Reference
2
Uses speed references d1-01 to d1-16 to set a multi-step speed reference.
Note:
Refer to Setting Procedures for Multi-step Speed Operation on page 225 for more information.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV

Table of Contents

Related product manuals