2.8 H: Terminal Function Selection
294 YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
OFF : Baseblock (drive output stop)
■ A: Accel/Decel Ramp Hold
Setting Value Function Description
A Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and d4-01 = 1 [Freq Reference Retention Select =
Enabled], the drive will store the output frequency in memory. While the acceleration/deceleration ramp hold
command is activated, the drive will always restart the motor at this output frequency.
Note:
Refer to d4-01: Freq Reference Hold Selection on page 233 for more information.
■ B: Overheat Alarm (oH2)
Setting Value Function Description
B Overheat Alarm (oH2)
Sets the drive to show an oH2 [External Overheat (H1-XX=B)] alarm when the input terminal is ON. The alarm does not have an
effect on drive operation.
■ C: Analog Terminal Enable Selection
Setting Value Function Description
C Analog Terminal Enable
Selection
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal Enable Sel].
ON : Terminal selected with H3-14 is enabled
OFF : Terminal selected with H3-14 is disabled
■ E: ASR Integral Reset
Setting Value Function Description
E ASR Integral Reset
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
■ F: Not Used
Setting Value Function Description
F Not Used
Use this setting for unused terminals or to use terminals in through mode.
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a communication
option or MEMOBUS/Modbus communications. This input signal does not have an effect on drive operation.
■ 10: Up Command
Setting Value Function Description
10 Up Command
Sets the command to use a push button switch to increase the drive frequency reference. You must also set Setting 11 [Down
Command].
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.