Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 303
OFF : Stop
Note:
If you turn ON the Forward Run command terminal and the Reverse Run command terminal, it will cause an EF [FWD/REV Run
Command Input Error] alarm and the motor will ramp to stop.
Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
This function will not operate at the same time as H1-xx = 42, 43 [Run Command (2-Wire Sequence 2), FWD/REV (2-Wire Sequence 2)].
42: Run Command (2-Wire Sequence 2)
Setting Value Function Description
42 Run Command (2-Wire
Sequence 2)
Sets the Run command for 2-wire sequence 2. Set this function and H1-xx = 43 [FWD/REV (2-Wire Sequence 2)] together.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward RUN (2-Wire), Reverse RUN (2-Wire)].
43: FWD/REV (2-Wire Sequence 2)
Setting Value Function Description
43 FWD/REV (2-Wire
Sequence 2)
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and H1-xx = 42 [Run Command (2-Wire Sequence 2)]
together.
ON : Reverse Run
OFF : Forward Run
Note:
You must input the Run command to rotate the motor.
This function will not operate at the same time as H1-xx = 40, 41 [Forward RUN (2-Wire), Reverse RUN (2-Wire)].
44: Add Offset Frequency 1 (d7-01)
Setting Value Function Description
44 Add Offset Frequency 1 (d7-
01)
Sets the function to add the offset frequency set in d7-01 [Offset Frequency 1] to the frequency reference when the terminal
activates.
Note:
Refer to d7: Offset Frequency on page 239 for more information.
45: Add Offset Frequency 2 (d7-02)
Setting Value Function Description
45 Add Offset Frequency 2 (d7-
02)
Sets the function to add the offset frequency set in d7-02 [Offset Frequency 2] to the frequency reference when the terminal
activates.
Note:
Refer to d7: Offset Frequency on page 239 for more information.
46: Add Offset Frequency 3 (d7-03)
Setting Value Function Description
46 Add Offset Frequency 3 (d7-
03)
Sets the function to add the offset frequency set in d7-03 [Offset Frequency 3] to the frequency reference when the terminal
activates.
Note:
Refer to d7: Offset Frequency on page 239 for more information.
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV
V/f
OLV
OLV/PM OLV/PM
AOLV/PM
EZOLV