Parameter Details
2
2.8 H: Terminal Function Selection
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING 311
Table 2.54 MEMOBUS MFDO Registers
Register number
(Hex.)
Name
15E0
bit0 MEMOBUS MFDO 1
bit1 MEMOBUS MFDO 2
bit2 MEMOBUS MFDO 3
Note:
Refer to MFDO Setting Values on page 318 for more information about MFDO setting values.
When you do not set functions to H2-40 to H2-42, set them to F.
Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use H2-60, H2-63, and H2-66 [Term MA,MB,MC Secondary Function, Terminal P1 Secondary Function, and
Terminal P2 Secondary Function] to set the function of the output signal for which you will perform logical
operations.
Use H2-61, H2-64, and H2-67 [Term MA,MB,MC Logical Operation, Terminal P1 Logical Operation, and Terminal
P2 Logical Operation] to set the logical operation.
Figure 2.66 Functional Block Diagram of Logical Operation Output for MFDO 1
Table 2.55 MFDO Logical Operation Table
Logical Operation Selection
Logical Operation Expression Logical Operation Notation
H2-61, H2-64, H2-67
0 A=B=1
1 A=1 or B=1
2 A=0 or B=0
3 A=B=0
4 A=B A=B
5 A != B
6
AND (A, )
7
OR (A, )
8 - On
Note:
If you use the function to output logical calculation results, you cannot set H2-01 to H2-03 = 1xx [Inverse Output of xx]. If you do, the drive
will detect oPE33 [Digital Output Selection Error].
When you do not use H2-60, H2-63, and H2-66, set them to F. The through mode function is not supported.